Appendix B: Installation Worksheet
Job Name:
HVAC system type:
Table 21: Advanced Configuration Parameters for the
Advanced
Applicable
Configuration
Systems
Parameter
01A
All
02A
06A
07A
All
(except
08A
for radiant
underfloor
11A
heat)
12A
18A
19A
All
20A
26A
27A
05A
FCUs with
multi-
speed fan
09A
Continued on next page...
Name
Description
0: Operate with thermostat
Function Type
1: Standalone
2: Not Configured
0: Flush mounted sensor connected to
Temperature
HVAC controller
Sensor Type
1: Thermostat sensor
Minimum Fan
Minimum time fan is on in auto mode (minutes)
On Time
Overrun Cool
Minutes the fan runs after cooling relay opens
Fan Time
Overrun Heat Fan
Minutes the fan runs after heating relay opens
Time
Time to delay start of fan after cooling starts.
Cool Fan on Delay
Only used with Fan Auto Speed when fan was
last off.
Time to delay start of fan after heating starts.
Heat Fan on Delay
Only used with Fan Auto Speed when fan was
last off.
0: Off
Standalone
1: Heat Only
Temperature
2: Cool Only
Operation Mode
3: Auto
0: Off
Standalone Fan
1: Low
Mode
2: Medium
(not applicable to
3: High
radiant floors)
4: Auto
5: Single Speed On
Remote Sensor
Temperature offset for remote temperature
Temperature
sensor. This allows for compensation based
Offset
on the installation location of the probe.
Cannot Reach
Cannot reach setpoint alarm time threshold
Setpoint Timeout
(minutes)
Cannot Reach
0: Alarm and keep trying
Setpoint Action
1: Alarm and enter failsafe
Auto fan mode temperature difference in
Fan High
degrees to switch from medium to high fan
Differential
speed
Kick-Start Fan
0: Off
(multi-speed
1: Set fan high for 1 second when turning on
fan only)
(continued)
SMC55-HWQS
36
Default Value
Range
2: Not Configured
0 – 2
1:Thermostat sensor
0 – 1
2 minutes
0 – 99
0 – 99.9
0 minutes
(minutes)
0 – 99.9
0.1 minutes
(minutes)
0 seconds
0 – 99
0 seconds
0 – 99
3: Auto
0 – 3
4: Auto
0 – 5
-5.0 –
0° F
+5.0
0.5 –
30 minutes
99.5
0: Alarm and keep
0 – 1
trying
0.1 –
1.5° F
10.0
0: Off
0 – 1
P/N 032498h
Value to
be Set