Step 5: Set the SMC55-HWQS Advanced Parameters to Modify the
Functionality of the HVAC System
lists out the details of all the advanced configuration parameters. Some of the advanced parameters are applicable to
Table 16
all types of HVAC equipment while some are applicable to a specific type of HVAC equipment. The table below also categorizes
these parameters based on the type of applicable systems.
Table 16: Advanced Configuration Parameters for the SMC55-HWQS
Advanced
Applicable
Configuration
Systems
Parameter
01A
All
02A
03A
06A
07A
All
(except
08A
for radiant
underfloor
11A
heat)
12A
18A
19A
All
20A
26A
27A
05A
FCUs with
multi-speed
fan
09A
Continued on next page...
Name
Description
0: Operate with thermostat
Function Type
1: Standalone
2: Not Configured
0: Flush mounted sensor connected to
Temperature
HVAC controller
Sensor Type
1: Thermostat sensor
Deadband
Inactive range above and below the Setpoint
Minimum Fan
Minimum time fan is on in auto mode (minutes)
On Time
Overrun Cool
Minutes the fan runs after cooling relay opens
Fan Time
Overrun Heat Fan
Minutes the fan runs after heating relay opens
Time
Time to delay start of fan after cooling starts.
Cool Fan on Delay
Only used with Fan Auto Speed when fan was
last off.
Time to delay start of fan after heating starts.
Heat Fan on Delay
Only used with Fan Auto Speed when fan was
last off.
0: Off
Standalone
1: Heat Only
Temperature
2: Cool Only
Operation Mode
3: Auto
0: Off
Standalone Fan
1: Low
Mode
2: Medium
(not applicable to
3: High
radiant floors)
4: Auto
5: Single Speed On
Remote Sensor
Temperature offset for remote temperature
Temperature
sensor. This allows for compensation based
Offset
on the installation location of the probe.
Cannot Reach
Cannot reach setpoint alarm time threshold
Setpoint Timeout
(minutes)
Cannot Reach
0: Alarm and keep trying
Setpoint Action
1: Alarm and enter failsafe
Auto fan mode temperature difference in
Fan High
degrees to switch from medium to high fan
Differential
speed
Kick-Start Fan
0: Off
(multi-speed
1: Set fan high for 1 second when turning on
fan only)
(continued)
19
Default Value
Range
2: Not Configured
(sets itself to 0
automatically when
0 – 2
connected to a
thermostat and basic
configuration is entered)
1: Thermostat sensor
0 – 1
1 °F
0.1 °F – 10 °F
2 minutes
0 – 99
0 – 99.9
0 minutes
(minutes)
0 – 99.9
0.1 minutes
(minutes)
0 seconds
0 – 99
0 seconds
0 – 99
3: Auto
0 – 3
4: Auto
0 – 5
0° F
-5.0 – +5.0
30 minutes
0.5 – 99.5
0: Alarm and keep trying
0 – 1
1.5 °F
0.1 – 10.0
0: Off
0 – 1
P/N 032498h