IDEAL 61-520 Operating Instructions page 2

Phase sequence and open phase indicator

Advertisement

CONTENTS
Page
2. Importance of Phase Sequence Indication; Specifications; Packaging
3. Front Panel View
4. How to Check Phase Sequence
5. How to Check Phase Sequence(cont'd.)
6. Warranty; Do's and Don'ts
IMPORTANCE OF PHASE SEQUENCE INDICATION
Phase Sequence is the order in which the phase voltages come on the
system.
If, during repair or maintenance, two lines are transposed (interchanged)
from their original positions, the Phase Sequence will be reversed. This, in
turn, will reverse the direction of all 3-Phase motors on the system.
This can cause severe personal, property and equipment damage especially
where rotating machinery is used for woodworking, metalworking, escalators,
elevators, automation, etc.
Hence, when any repairs or maintenance is made on 3-Phase systems, or
when paralleling 3-Phase Transformers or 3-Phase banks, the phase
sequence of each must be in the same order.
The Model 61-520 is a positive action electrical tester and will indicate
both Phase Sequence and Phase Continuity instantly and accurately.
SPECIFICATIONS
Voltage
- to 600V on 3-Phase Power Source
Duty Cycle
- CONTINUOUS TO 500V
5 MINUTES MAX. FROM 500V TO 600V
Frequency
- 50/60Hz
Insulation
Test
- 2,200V AC for 1 minute
Dimensions - 4.24"L X 3"W X 1.6" D (106X75X40mm)
Weight
- 12
/
Oz. (350g.)
1
2
Line Cord
- 60"
PACKAGING
Packed in handy unit box, complete with Pouch, Form ND-1714 Operating
Instructions and Warranty Card, all ready to use.
HOW TO CHECK PHASE SEQUENCE (cont'd)
1. Please note the 3 'Open Phase' Check Lamps
at the bottom of the front panel.
The alligator clip with Red Insulator is internally
connected to the left lamp with Phase Designa-
tion 'R'; the White Insulator to the middle lamp
with Phase Designation 'S'; the Blue Insulator
to the right lamp with Phase Designation 'T'.
2. Connect the 3 alligator clips to the 3-Phase Power source being
checked for Phase Sequence. The positions of the clips on the 3
lines is optional.
3. Press the 'ON' button in lower right corner of front panel, keeping
it depressed throughout the test.
4. If all 3 lamps are lit, it signifies NO OPEN PHASES and the Phase
Sequence can then be checked.
However, if any of the lamps are NOT lit, the Phase Sequence
Indicator will not operate. Check to determine cause of the open
phase and correct before proceeding with the test.