CC-Link interface module
Figure 3:
Mounting the module
onto the DIN rail
Figure 4:
Installing the end clips
Make sure that the voltage supply of the MELSEC-WS safety controller is
switched off.
Hang the device onto the DIN rail (1)).
Connect the CC-Link interface module directly onto the right side of the CPU
module of the MELSEC-WS safety controller. Up to two network modules per
system are possible.
Ensure that the earthing spring contact is positioned correctly (2)). The earthing
spring contact of the module must contact the DIN rail securely to allow
electrical conductivity.
Latch the module onto the DIN rail by pressing it lightly in the direction of the
arrow (3)).
If there are several modules, slide the modules together individually in the
direction of the arrow until the side plug connection latches in.
Install the end clips on the right and left.
The following steps are necessary after mounting:
Complete the electrical connections (See Section 4.3.)
Configuration (See Section 4.5 and the Safety Controller Setting and Monitoring
Tool Operating Manual.)
Checking the installation (See the Safety Controller User's Manual.)