Date/Time - Siemens SENTRON PAC3120 Manual

7km power monitoring device
Hide thumbs Also See for SENTRON PAC3120:
Table of Contents

Advertisement

Current input
Selection
CT PRIMARY
CT SECONDARY
DISPLAY RANGE:
7.2.4

Date/time

Setting the date and time
Selection
DATE
FORMAT
TIME
TIME ZONE
PAC3120 and PAC3220
Equipment Manual, 10/2019, L1V30425208F-01
CURRENT DIREC L1
CURRENT DIREC L2
CURRENT DIREC L3
7.2 Parameterizing via the operator interface
Range
Primary current of the current transformers
1 ... 99999 A
Secondary current of the current transformers
1 A
5 A
Freely adjustable
1 ... 99999 A
Inverse evaluation of the current flow direction
separately for each phase.
ON: Direction of current flow is inverted.
The device interprets the current flow direc-
tion as opposite to the wiring.
OFF: The device interprets the current
flow direction to match the wiring.
Range
Current date.
The date format is defined in the FORMAT field.
DD.MM.YYYY
YYYY-MM-DD
MM/DD/YY
HH:MM:SS
Time zone, refers to coordinated universal time
(UTC).
−12:00 ... +14:00, in 30-minute intervals
Examples:
"−06:00" corresponds to UTC-6
"+01:00" corresponds to UTC+1
Parameter assignment
Factory setting
50 A
5 A
50 A
OFF
Factory setting
DD.MM.YYYY
00:00
73

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sentron pac3220

Table of Contents