Compliance With Codes - Patterson-Kelley SOLIS SL-1500 Installation & Owner's Manual

Gas fired boiler with control system
Table of Contents

Advertisement

2.3 Compliance with Codes

Each P-K SOLIS™ boiler with standard components complies with American National Standard/CSA
Standard ANSI Z21.13/CSA 4.9, latest edition for Gas-Fired Low Pressure Steam and Hot Water
Boilers.
The P-K SOLIS™
SL-1500, SL-2000, SL-2500, and SL-3000
stamped in accordance with ASME Boiler and Pressure Vessel Code, Section IV for 160 psig maximum
pressure and 210°F maximum temperature. Other codes or approvals which apply will be labeled on
the boiler.
Code of Construction
(Boiler)
Maximum Allowable Working
Pressure
Maximum Allowable Design
Temperature
Hi-Limit Setpoint
Maximum Setpoint
Installation of the boiler must conform to all the requirements of all national, state and local codes
established by the authorities having jurisdiction or, in the absence of such requirements, to the
National Fuel Gas Code, ANSI Z223.1/NFPA 54 latest edition in the U.S. In Canada, the equipment
shall be installed in accordance with the current Installation Code for Gas Burning Appliances and
Equipment, CAN/CSA-B.149, latest edition, and applicable Provincial Regulations for the class, which
should be carefully followed in all cases. Authorities having jurisdiction should be consulted before
making any installation.
Where required by local codes, the installation must conform to American Society of Mechanical
Engineers Safety Code for Controls and Safety Devices for Automatically Fired Boilers (ASME CSD-1).
In the Commonwealth of Massachusetts (a) this unit must be installed by a licensed pipe fitter/plumber,
(b) field installed gas cocks must be "T" handle type, (c) piping of condensate shall conform to the State
Plumbing Code, and (d) refer to the Massachusetts Supplement for further details.
Revised: March 15, 2021
Released: March 15, 2021
SL-1500, SL-2000, SL-2500, & SL-3000
ASME Section IV – "H"
© Patterson-Kelley 2021
All Rights Reserved.
P-K SOLIS™
Technical Service 1.877.728.5351
heat exchangers are constructed and
(Latest Edition)
160 PSIG
210° F
200° F
185° F
2701000090 P-K SOLIS NURO Installation and
Owners Manual (Rev A).docx
Gas Fired Boiler
Page 3