INSTALLATION
Connecting a Door
3a
Connect the Lock (Dry)
For a dry setup, please ensure that "NONE" is selected on the door power selection switch.
Fail Safe
3b
Connect the Lock (Wet)
In a Wet configuration, ensure that power selection
for each door is set to the correct voltage as outlined
by the locking hardware specifications.
•
Set it to "12VDC" for 12 Volt locking hardware
•
Set it to "24VDC" for 24 Volt locking hardware
The AC41 is rated to power 12V locks up to 700mA
and 24V locks up to 350mA.
Fail Safe
•
LOCK (+) positive goes into NC
•
LOCK (-) negative and ground wire goes into COM
CONFIDENTIAL
Fail Secure
Fail Secure
•
•
Verkada Inc. 405 E 4th Ave, San Mateo, CA, 94401
sales@verkada.com
WARNING!
When connecting the lock in the Wet
configuration, ensure the negative of the
lock goes into the COM port as shown in
the diagrams below.
LOCK (+) positive goes into NO
LOCK (-) negative and ground wire goes into COM
All specifications are subject to change without notice.
Copyright © Verkada Inc . All rights reserved.
AC41 — INSTALLATION MANUAL