Summary of Contents for Verkada AC41

  • Page 1 AC41 Door Access Controller...
  • Page 2: What You'll Need

    In the box 1 AC41 Door Access Controller 1 Wall mount plate 1 T10 security torx screwdriver 4 Mounting screws and wall anchors What you’ll need • A working wired internet connection over ethernet • A smartphone or laptop • A #2 Phillips screwdriver or power drill with a #2 Phillips driver bit •...
  • Page 3 Door security screw AC41 Power cable exit Access control cable exit Wall mount AC41 Overview Cable mangement box Door contact switch Wall mount Power cable exit Access control security screws cable exit...
  • Page 4 Toggle between doors Active door Status LED Test lock Test DPI Test REX Door status LED Removeable AC41 Details Dry / 12V / 24V cassette selection switch Dual USB 2.0 Power Power supply monitor Dual Ethernet...
  • Page 5 AC41 Cassettes Remove all 5 cassettes from their packaging and insert into the AC41. Ensure the USB-C and other mating features are aligned for correct fitment.
  • Page 6 AC41 Mounting To remove the wall mount, unscrew the two security torx screws from the inside.
  • Page 7 Drill four 5/16” Ø holes into the wall. Insert the drywall anchors into the holes. Fasten the Once the security screws are fully removed, slide the wall mount down mount plate onto the wall by installing the mounting screws into the wall anchors. and away from the main enclosure.
  • Page 8 Place the sheet metal enclosure over and onto the mounting plate tabs. Fasten the two security torx screws to secure the enclosure to the mounting plate. 14 - mount mount - 15...
  • Page 9 The AC41 comes equipped with a Form C relay that can be driven dry or wet. AC41 is rated to power 12V locks up to 700mA and a 24V locks up to 350mA. AC41 Connect Door...
  • Page 10 LOCK ( + ) positive [12V / 24V] goes into NC (fail safe) or NO (fail secure) LOCK power supply goes into COM 12V/24V+ Lock Lock power supply Remove a door cassette from the AC41 by lifting it from the side tabs. 12V/24V+ Lock 18 - connect door connect door - 19...
  • Page 11 Connect the Lock (Wet 12V / 24V NO-C) Connect the Lock (Wet 12V / 24V NC-C) If you have a Fail Secure lock, connect to NO-COM. If you have a Fail Safe lock, connect to NC-COM. Lock Lock 20 - connect door connect door - 21...
  • Page 12 Connect the Reader Connect the Inputs Verkada AD31 reader (far left port) Door Position Indicator (Door Contact), optional Standard Wiegand readers (middle input port) Request-to-Exit (REX), optional 22 - connect door connect door - 23...
  • Page 13 AC41 Connect Connect the AC41 to your network using either of the Ethernet ports located at the bottom of the controller. If you are adding an additional AC41 unit to your system, you can connect ACUs by Ethernet.
  • Page 14 Flashing orange Controller is updating firmware Flashing blue Controller is managing doors, but cannot reach the server Connect the AC41 power supply into your standard power outlet (120 VAC). For detailed installation instructions, visit www.verkada.com/support Solid blue Controller is managing doors...
  • Page 15 To make installation easier, the AC41 has four buttons to help test or emulate different events. Pressing the “Door” button will cycle which door is selected for testing. AC41 Test Setup Trigger the lock relay on the selected door by clicking “Trigger Lock”...
  • Page 17 +1 (833) 837-5232 support@verkada.com www.verkada.com/support...