FusionModule1000A20 CT Solution
Maintenance Guide
Procedure
Step 1 Install the app on the spare pad and connect the pad to the network over the WiFi hotspot of
the data center.
Step 2 Specify the user name and password for the APP on the spare pad and log in to check that the
app works properly.
Step 3 Remove the old pad from the support and install the spare pad on the support.
----End
Follow-up Procedure
Dispose of the removed pad that is confirmed faulty.

5.3.15 (Optional) Replacing a CIM

Prerequisites
A spare CIM of the same model is available and functional.
Impact on the System
None
Preparations
Tool: Phillips screwdriver
Materials: spare CIM
Documents: iBAT 2.0-CIM01C2 User Manual
Skill requirement: extra low voltage (ELV) engineer
Procedure
Step 1 Clear the network parameters for all the BIMs managed by the CIM to be replaced.
Step 2 Remove and label CIM cables.
Step 3 Remove the CIM from the fastener.
Issue 01 (2019-02-25)
If the CIM is damaged, manually clear the network parameters for all the BIMs managed
by the CIM by holding down the networking switch for the BIM.
If the CIM is not damaged, hold down the networking switch for the CIM to clear the
current network (including the network parameters for all the BIMs managed by the CIM).
Copyright © Huawei Technologies Co., Ltd.
5 Parts Replacement