WIRING INSTRUCTIONS
■ APPLICABLE WIRE SIZE
• Solid: 0.2 to 1.0 mm
(0.55 to 1.12 dia.)
2
• Stranded: 0.2 to 1.5 mm
2
(Tinning wire ends may cause contact failure and therefore
is not recommended.)
• Ferruled:
Unsheathed: 0.25 to 1.5 mm
Sheathed: 0.25 to 0.75 mm
• Expose wire conductors by 10 mm (0.39").
Stripped length
10mm
■ CONNECTION PROCEDURE
Insert the wire end until it comes to a full stop while push-
ing slot with the tip of a screw driver as shown below. Be
sure wire insulation is not inside the terminal.
OUTPUT PIN ASSIGNMENT
PIN No.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
2
2
Screw Driver
Power wire
FUNCTION
Do 1
COM 1
Do 2
COM 2
Do 3
COM 3
Do 4
COM 4
Do 5
COM 5
Do 6
COM 6
Do 7
COM 7
Do 8
COM 8
+24V
+24V
0V
0V
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp
DATA ASSIGNMENT
■ Do
15
FUNCTIONS
■ OUTPUT HOLD or OUTPUT OFF
In normal conditions, the module outputs the signal from
the preferred bus A.
When an error is detected, the output is switched to the
data from the bus B.
• Output Hold
If both are in error, the module holds the signal and
stands by until one of the communications recovers.
• Output OFF
If both are in error, the module outputs OFF signals and
stands by until one of the communications recovers.
At the startup, it outputs OFF until the communication is
established and normal data is received.