SPECIFICATIONS

MODEL NUMBER: TAG-5000
OPERATING VOLTAGE RANGE: 4 - 230kV line-to-line
OPERATING FREQUENCY AND PHASING: Can be used on 50Hz and 60Hz systems
In phase indication for phase angle shift ≤ 10°
No in phase indication for phase angle ≥ 30°
TRANSMISSION: Radio frequency: 433.9MHz
OPERATING TEMPERATURE RANGE: -20F to +120F
WEIGHT: 1.2 lb. each unit with overhead probe

MAINTENANCE AND CARE

BATTERY The batteries require checking prior to each use. Use the All-Check button to
confirm proper operation. The All-Check button tests the battery voltage in addition to
the electronic circuitry, so it is a good test of battery strength. If the All-Check button does
not cause the lights to flash and the alarm to sound, replace the batteries with lithium or
alkaline types only.
STORAGE It is recommended for protection of the TAG-5000 that you always store
it and its accessories in the carrying case provided.
CLEANLINESS The molded housings are very rugged but should be kept clean
and free of dirt, grease and any other foreign materials. If the housings' surface
integrity has been compromised in any way, remove from service and return to
factory for repair or replacement.
WARNING: DO NOT USE SOLVENTS OF ANY KIND FOR CLEANING.
DAMAGE If you suspect any mechanical or electrical damage, do not use the
TAG-5000 and arrange for repair by returning to the factory.
CALIBRATION & TESTING Regular calibration of the TAG-5000 is not required.
There is no accessible calibration adjustment.
SERVICE Return to HD Electric Company for service.
10
Transmission power: < 10mW
Range: Over 33 feet through the air, over 1000 feet along overhead
conductors and underground cables with polyethylene
insulation; range is substantially reduced in underground
conductors with rubber insulation.

Advertisement

loading