IFM Efector 500 PM2655 Operating Instructions Manual

IFM Efector 500 PM2655 Operating Instructions Manual

Electronic pressure sensor
Table of Contents

Advertisement

Available languages

Available languages

Quick Links

Bedienungsanleitung
Operating instructions
Notice utilisateurs
R
Elektronischer
Drucksensor
Electronic pressure
sensor
Capteur de pression
électronique
PM2655

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Efector 500 PM2655 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for IFM Efector 500 PM2655

  • Page 1 Bedienungsanleitung Operating instructions Notice utilisateurs Elektronischer Drucksensor Electronic pressure sensor Capteur de pression électronique PM2655...
  • Page 2: Table Of Contents

    Inhalt 1 Bestimmungsgemäße Verwendung ... . . Seite 3 2 Verwendung im Auslieferungszustand ..Seite 4 Montage ........Seite 4 Elektrischer Anschluß...
  • Page 3: Bestimmungsgemäße Verwendung

    Sicherheitshinweise Lesen Sie vor der Inbetriebnahme des Gerätes die Produktbeschreibung. Vergewissern Sie sich, daß sich das Produkt uneingeschränkt für die betreffende Applikationen eignet. Die Mißachtung von Anwendungshinweisen oder technischen Angaben kann zu Sach- und/oder Personenschäden führen. Prüfen Sie in allen Applikationen die Verträglichkeit der Produktwerkstoffe (s.
  • Page 4: Verwendung Im Auslieferungszustand

    Prozeßanschlüsse. G1-Prozeßadapter sind geson- dert als Zubehör zu bestellen. Einschweißadapter Schweißen Sie zuerst den Adapter ein. Montieren Sie dann den Sensor. ifm-Prozeßadapter Montieren zuerst Adapter (B) an den Sensor, dann Sensor + Adapter mit Hilfe einer Überwurfmutter, eines Klemmflanschs o. ä. (A) an den Prozeßanschluß.
  • Page 5 Schalten Sie die Anlage spannungsfrei und schließen Sie das Gerät folgendermaßen an: 2-Leiter-Anschluß 3-Leiter-Anschluß Steckeransicht (am Gerät) n.c. n.c. n.c. Adernfarben bei ifm-Kabeldosen: 1 = BN (braun), 2 = WH (weiß), 3 = BU (blau), 4 = BK (schwarz); n.c. = nicht belegt.
  • Page 6: Inbetriebnahme / Betrieb / Wartung

    2 Verwendung im Auslieferungszustand Inbetriebnahme / Betrieb / Wartung Prüfen nach Montage, elektrischem Anschluß Programmierung, ob das Gerät sicher funktioniert. Reinigen der Filterabdeckung Sollten zähflüssige und rück- standbildende Medien Filterabdeckung Sensors zusetzen (und damit Meßgenauigkeit geringfügig beeinträchtigen), können Sie die Abdeckung reinigen.
  • Page 7: Sensor Programmieren / Betrieb Mit Eps-Interface

    Sensor programmieren / Betrieb mit EPS-Interface EPS-RS232-Interface Verbinden Sie den Sensor über das EPS-RS232-Interface (Bestell-Nr. E30066) mit einem PC. • Der Sensor wird vom Interface mit Betriebsspannung versorgt, • und überträgt über das Interface kontinuierlich seine Daten (Meßwerte, Analogsignal und Parameter-Einstellungen). Es bieten sich damit folgende Möglichkeiten: •...
  • Page 8: Elektrischer Anschluß (Sensor - Eps-Interface)

    1 = BN (braun), 2 = WH (weiß), 3 = BU (blau), 4 = BK (schwarz) n.c. = nicht belegt Programmieren Zum Programmieren des Sensors nutzen Sie bitte das FDT-Service- Programm ifm-container (Bestell-Nr. E30110). EPS-RS232-Interface, das Service-Programm ifm-container, Netzteil und Verbindungskabel sind als Set erhältlich (Bestell-Nr. ZZ0050).
  • Page 9: Technik-Information / Funktionsweise / Parameter

    Technik-Information / Parameter / Funktionsweise Einstellbare Parameter Analogstartpunkt Meßwert, bei dem 4 mA ausgegeben werden. Analogendpunkt Meßwert, bei dem 20 mA ausgegeben werden. Mindestabstand zwischen ASP und AEP = 25% der Meßspanne Einstellbereiche: in Schritten von -0,99 ... 1,00 0,26 ... 4,00 0,01 -14,4 ...
  • Page 10: Technische Daten

    4 Technik-Information / Parameter / Funktionsweise Einstellbare Parameter (Fortsetzung) Einstellung der Anzeige d1 / d2 / d3 = Meßwertaktualisierung alle 50 ms / 200 ms / 600 ms. Die Meßwertaktualisierung betrifft nur die Anzeige. Ph = kurzeitig festgehaltene Anzeige des Spitzen-Meßwerts (peak hold).
  • Page 11: Skalieren Des Meßbereichs

    Technik-Information / Parameter / Funktionsweise Skalieren des Meßbereichs • Mit dem Parameter Analogstartpunkt (ASP) legen Sie fest, bei wel- chem Meßwert das Ausgangssignal 4 mA beträgt. • Mit dem Parameter Analogendpunkt (AEP) legen Sie fest, bei wel- chem Meßwert das Ausgangssignal 20 mA beträgt. •...
  • Page 12 Contents 1 Function and features ..... . page 13 2 Use with factory setting ....page 14 Installation .
  • Page 13: Function And Features

    Safety instructions Read the product description before installing the unit. Ensure that the product is suitable for your application without any restrictions. Non-adherence to the operating instructions or technical data can lead to personal injury and/or damage to property. In all applications check compliance of the product materials (see Technical data) with the media to be measured.
  • Page 14: Use With Factory Setting

    Welding adapter Weld the adapter first. Then mount the sensor. ifm process adapter Mount adapter (B) to the sensor first, then sensor + adapter to the process connection by means of a nut, a clamping flange or similar (A).
  • Page 15: Electrical Connection

    Disconnect power before connecting the unit as follows: 2 wire connection 3 wire connection Connector view (sensor) n.c. n.c. n.c. Core colours of ifm sockets: 1 = BN (brown), 2 = WH (white),3 = BU (blue), 4 = BK (black); n.c. = not connected.
  • Page 16: Installation And Set-Up / Operation / Maintenance

    2 Use with factory setting Installation and set-up / operation / maintenance After mounting, wiring and setting check whether the unit operates correctly. Cleaning of the filter cover If viscous and residues producing media clog the filter cover of the sensor (and thus reduce the mea- suring accuracy slightly), you can clean it.
  • Page 17: Programming / Use With Eps Interface

    Programming / Use with EPS RS232 interface EPS RS232 interface Connect the sensor to a PC via the EPS-RS232 interface (order no. E30066). • The sensor is supplied with operating voltage by the interface, • and transmits its data (measured values, analogue signal and para- meter settings) continuously via the interface.
  • Page 18: Electrical Connection (Sensor - Eps Interface)

    Wiring of sensor and EPS interface For use of the sensor with EPS interface prior to installation of the sen- sor: Use a suitable power supply (24 V power supply; ifm order no. E30080). For mobile use of the interface after installation of the sensor: Disconnect power before connecting the unit.
  • Page 19: Technical Informations / Functioning / Parameters

    Technical information / Functioning / Parameters Adjustable parameters Analogue start point Measured value at which 4 mA is provided. Analogue end point Measured value at which 20 mA is provided. Minimum distance between ASP and AEP = 25% of the span. Setting range: in steps of -0.99 ...
  • Page 20: Technical Data

    4 Technical information / Functioning / Parameters Adjustable parameters (continuation) Setting of the display d1 / d2 / d3 = update of the measured value every 50 ms / 200 ms / 600 ms. The update interval only refers to the display. ph = display of the measured peak value remains for a short time (peak hold).
  • Page 21: Scaling The Measuring Range

    Technical information / Functioning / Parameters Scaling the measuring range • With the parameter "Analogue start point" (ASP) the measured value at which the output signal is 4 mA is defined. • With the parameter "Analogue end point" (AEP) the measured value at which the output signal is 20 mA is defined.
  • Page 22 Contenu 1 Fonctionnement et caractéristiques ... . page 23 2 Utilisation avec réglage usine ....page 24 Montage .
  • Page 23: Fonctionnement Et Caractéristiques

    Remarque sur la sécurité Avant la mise en service de l'appareil, veuillez lire la descrip- tion du produit. Assurez-vous que le produit est approprié pour l'application concernée sans aucune restriction. Le non-respect des remarques ou des données techniques peut provoquer des dommages matériels et/ou corporels. Pour toutes les applications, veuillez vérifier la compatibilité...
  • Page 24: Utilisation Avec Réglage Usine

    Adaptateurs G1 à commander séparément comme accessoires. Adaptateur de soudage Souder d'abord l'adaptateur. Monter ensuite le capteur. Adaptateurs process ifm Monter d'abord l'adaptateur (B) sur le capteur, ensuite le capteur et l'adaptateur sur le raccord process à l'aide d'un écrou, d'une flasque de serrage ou simi- laire (A).
  • Page 25: Raccordement Électrique

    2 fils raccordement 3 fils branchement connecteur n.c. n.c. n.c. Couleurs des fils conducteurs des connecteurs femelles ifm: 1 = BN (brun), 2 = WH (blanc), 3 = BU (bleu), 4 = BK (noir).; n.c. = non raccordé.
  • Page 26: Mise En Service / Fonctionnement / Maintenance

    2 Utilisation avec réglage usine Mise en service / Fonctionnement / Maintenance Après le montage, le câblage et le réglage vérifier le bon fonctionne- ment de l'appareil. Nettoyage du couvercle du système de filtrage Si des fluides visqueux qui pro- duisent des résidus bouchent le couvercle du système de filtrage du capteur (et donc réduisent...
  • Page 27: Programmation / Capteur Avec Interface Eps-Rs232

    Programmation / Capteur avec interface EPS-RS232 interface EPS-RS232 Raccorder le capteur à un PC via l'interface EPS-RS232 (n° de com- mande E30066). • Le capteur est alimenté en tension par l'interface • et transmet ses données (valeurs mesurées, signal analogique et paramètres réglés) continuellement via l'interface.
  • Page 28: Raccordement Électrique (Capteur - Interface Eps)

    EPS-RS232 n.c. GND 2 capteur Couleurs des fils conducteurs des connecteurs femelles ifm: 1 = BN (brun), 2 = WH (blanc), 3 = BU (bleu), 4 = BK (noir). n.c. = non raccordé. Programmation Pour programmer le capteur, veuillez utiliser le programme de service FDT ifm container (référence E30110).
  • Page 29: Informations Techniques / Fonctions / Paramètres

    Informations techniques / Fonctions / Paramètres Paramètres réglables Valeur minimum de la sortie analogique Valeur mesurée dont le signal de sortie est 4 mA. Valeur maximum de la sortie analogique Valeur mesurée dont le signal de sortie est 20 mA. Ecart minimum entre ASP et AEP = 25% du gain.
  • Page 30: Données Techniques

    4 Informations techniques / Fonctions / Paramètres Paramètres réglables (continuation) Réglage de l'afficheur d1 / d2 / d3 = actualisation de la valeur mesurée toutes les 50 ms / 200 ms / 600 ms. L'actualisation ne change que l'intervalle d'actualisation de l'affichage. ph = affichage de la valeur maxi mesurée pour un bref délai (peak hold).
  • Page 31: Réglage De L'étendue De Mesure

    Informations techniques / Fonctions / Paramètres Réglage de l'étendue de mesure • Par le paramètre "Valeur minimum de la sortie analogique" (ASP) on peut sélectionner la valeur mesurée à laquelle le signal de sortie est 4 mA. • Par le paramètre "Valeur maximum de la sortie analogique" (AEP) on peut sélectionner la valeur mesurée à...
  • Page 32: Maßzeichnung

    Maßzeichnung Scale drawing Dimensions M12 x1 25,4 20° 1 Anzugsdrehmoment 20 Nm 1 Tightening torque 20 Nm 1 Couple de serrage maxi 20 Nm...