Select "AC" label in the panel configuration page, as shown in Figure 4-1.

4.1 General Setting

Select "Enable" at the top of AC setting part (Mark ① of Figure 4-1) to enable AC.
➢ Subnet ID
➢ Device ID
➢ Status when power on: when "OFF" is selected, AC will be OFF when the panel is
powered on. When "Last status" is selected, AC will be in the status before the last power
off when the panel is powered on.
➢ HVAC No.: to enter corresponding AC number to control, which ranges from 1 to 128, the
default number is 1.
➢ Type: Version 1 (not support HVAC no.) and Version 2 (support HVAC no.).
➢ Adjust: to set temperature compensation for correcting temperature data detected by the
panel, which ranges from -8 to 8. For example, when the standard thermometer shows
20℃ while the panel shows 22℃, the temperature compensation should be set to -2℃.