Feedback" or "Ask Feedback", user may set the subnet ID, device ID and channel of
external sensor.
➢ Average of In & Out: the panel refers to the average of temperature from internal and
external sensor, the temperature of up to 2 external sensor can be referred to at a
time.
➢ Protection temperature: when the temperature exceeds the preset protection value,
the panel will turn off floor heating. The protection temperature ranges from 5 to 80℃.
➢ Outdoor temperature: to set temperature source for obtaining temperature. If
selecting "Receive Feedback" or "Ask Feedback", user may set the subnet ID, device
ID and channel of external sensor.
③ Temperature range from: user may customize the working temperature range of floor
heating, the default range is from 5℃ to 35℃.
④ Working setting:
➢ Output: to select "Relay ON/OFF" or "PWM Value".
➢ Min.-Max. PWM: to set PWM value range.
➢ Heating speed: to set the heating speed of floor heating.
➢ Control cycle: to set the control period of the relay and PWM, whose ranges both are
from 1 to 20 minutes.
➢ Day/Night start at: timer mode includes Day/Night mode, floor heating automatically
enters Day/Night mode at the set time in "Day/Night start at".
➢ Mode: to enable 5 work modes.
➢ Mode changeover (auto mode-between floor heating and floor cooling):
1. Auto mode triggering temperature deviant value: after auto mode is selected,
user may set temperature deviant value to enable switching between floor
heating/cooling. Temperature deviant value ranges from 1℃ to 5℃.
For example, set the temperature in auto mode to 20℃ and temperature deviant
value to 2℃, when the ambient temperature exceeds 22℃, floor cooling will be
activated. When the ambient temperature is under 18℃, floor heating will be
activated.
2. Enable PID: select to enable PID.
3. Always ON: select to lock floor heating running, floor heating will keep on all the
time.
4. Sync command: to enable/disable broadcasting. After selecting the option, other
panels can synchronize the panel information after reception.