  • Page 3 User Manual HDL-MP8B-RF.18 INDEX 1. Overview............................1 1.1 General Information......................1 1.2 Functionalities Description....................1 1.3 Device Description......................2 2. Safety Instructions........................2 3. Technical Data..........................2 4. Installation............................3 5. Software Configuration........................4 5.1 Basic Information....................... 4 5.1.1 Wireless Setting via Mesh Gateway..............4 5.1.2 Indicator Intensity....................5 5.2 Key Assignation........................5...
  • Page 4: Overview

    HDL-MPT4-RF.18 1. Overview 1.1 General Information Wireless 4 buttons touch panel HDL-MPT4-RF.18 is a multi-functional control panel, embedded with RGB LED backlight for each touch button, any color is available for the button via setting in HDL Buspro Setup Tool.
  • Page 5: Device Description

    User Manual HDL-MPT4-RF.18 1.3 Device Description 10.5 Touch button Touch button Signal interface Fastener Split gap Front view Side view Back view 2. Safety Instructions  The screw down strength should not exceed 0.1Nm  Mounting position: Indoor.  Never let liquids get into the module, it will damage this device.
  • Page 6: Installation

    User Manual HDL-MPT4-RF.18 Working temperature -5℃~45℃ Working relative humidity Up to 90% Storage temperature -20℃~+60℃ Storage relative humidity Up to 93% Approved RoHS Production Information Dimensions 86×86×10.5 (mm) Weight 110(g) Housing material Glass Installation Wireless power interface, EU wall box...
  • Page 7: Software Configuration

    User Manual HDL-MPT4-RF.18 Wall box: For convenience of the wiring installation, the wall box should be a little deeper than the power interface. 5. Software Configuration 5.1 Basic Information 5.1.1 Wireless Setting via Mesh Gateway Before user can configure the wireless panel normally, need to set the wireless parameters for it via mesh gateway, and the mesh gateway needs to work in mesh mode.
  • Page 8: Indicator Intensity

    7- Click ‘all Node Exit Setup’, then the wireless devices will exit the wireless setup mode. 8- Go to the HDL BUS setup tool’s main interface to search and add the panel, then can start to configure it via the gateway.
  • Page 9: Remark

    User Manual HDL-MPT4-RF.18 5.2.1 Remark Do the remark for each key for easy management. Wireless 4 buttons Touch Panel – User Manual...
  • Page 10: Mode

    User Manual HDL-MPT4-RF.18 5.2.2 Mode Key mode: Single on Assign the Switch can turn on one target only (one channel, one scene, one sequence, etc.) Single off Assign the Switch can turn off one target only (one channel, one scene, one sequence, etc.)
  • Page 11: Function

    User Manual HDL-MPT4-RF.18 Double click can control up to 49 targets, single click only control 1 target Dblclick/combination switch Both double click and combination switch can control up to 49 targets Momentary Press to turn on target, release to turn off target.
  • Page 12 Can be used to do some basic settings for the device from panel, like changing the logic input conditions of, e.g., 12in1 Sensor, rather than using HDL-BUS Pro Setup Tool, this feature makes the system more flexible for end-user. For more info, please refer to universal control command_ 12in1.xls, download from:...
  • Page 13: Key Linkage

    User Manual HDL-MPT4-RF.18 IR control For HDL Matrix device (not ready to use) Logic light Adjust For HDL-MLED0605.432, 48DMX and 512DMX module Logic Scene For HDL-MLED0605.432, 48DMX and 512DMX module 5.2.4 Key Linkage Below screen shot shows the mutual exclusion and key linkage functions: Mutual exclusion: The key combination mode such as combination on, combination on/off can be set to mutual exclusion.
  • Page 14: Key Lock

    User Manual HDL-MPT4-RF.18 Steps: button 1 : mode single on button 1 : single channel control ON button 2 : mode single off button 2 : single channel control OFF Key linkage…: please link button 1 to itself, button 2 to 1.
  • Page 15: Ir And Other Functions

    Invalid - Disable the LED indicator of the key 5.2.7 IR and Other Functions Infrared receiving function status Enable/disable the IR receiving function (accept HDL remote controller only) Minimum dimming value Set the dimming lower limit. The Lower limit is useful if you would like to skip the low level segment and dim from a...
  • Page 16: Test The Switch

    User Manual HDL-MPT4-RF.18 certain level, say 40%. You want to skip it because maybe lower than 40% is impractical for you or maybe the load quality is not so good and trembles when at low level segment. Long press time Set time for long-press, define the long press by end-user.
  • Page 17: Button Status Light Color Set

    User Manual HDL-MPT4-RF.18 5.6.2 Button Status Light Color Set Set the ON/OFF status color for each button. 5.6.3 White balance adjust For some panels, the displaying LED color has little difference from the one you set, user can adjust its white color with this function. After adjusted, all colors can be indicated correctly.
  • Page 18 User Manual HDL-MPT4-RF.18 Remark: Remark the channel for the easy management. Load Type: Select the corresponding load type for each channel according to the real situation; it is just like a remark, would not affect the behavior of lamps. Default selection – Undefined.
  • Page 19: Dimmer Setting

    User Manual HDL-MPT4-RF.18 7. Dimmer Setting Dimmer Turnoff Temperature: Set the temperature for protection, when the panel’s detected temperature reaches to the setting temperature, it will turn off the connected loads automatically. When the detected temperature is lower than the setting temperature, it will restore the loads’ status again.
  • Page 20: Online Upgrade

    User Manual HDL-MPT4-RF.18 8. Online Upgrade Wireless touch panels supports automatic upgrade, does not support manually upgrade. Automatic Upgrade Upgrade steps: 1- Select the online wireless panel that you want to upgrade, click “Read Device Type” to check its chip type.
  • Page 21: Note

    User Manual HDL-MPT4-RF.18 9. Note ………………………………………………………………………………………………………. ……………………………………………………………………………………………………… ……………………………………………………………………………………………………… ……………………………………………………………………………………………………… ……………………………………………………………………………………………………… ……………………………………………………………………………………………………… ……………………………………………………………………………………………………… ……………………………………………………………………………………………………… ……………………………………………………………………………………………………… ……………………………………………………………………………………………………… ……………………………………………………………………………………………………… ……………………………………………………………………………………………………… ……………………………………………………………………………………………………… ……………………………………………………………………………………………………… ……………………………………………………………………………………………………… ……………………………………………………………………………………………………… ……………………………………………………………………………………………………… ……………………………………………………………………………………………………… ……………………………………………………………………………………………………… ……………………………………………………………………………………………………… ……………………………………………………………………………………………………… ……………………………………………………………………………………………………… ……………………………………………………………………………………………………… ……………………………………………………………………………………………………… ……………………………………………………………………………………………………… ……………………………………………………………………………………………………… ……………………………………………………………………………………………………… Wireless 4 buttons Touch Panel – User Manual...