Page 1
User Manual WISE-2410 LoRaWAN Smart Condition Monitoring Sensor...
Page 2
The documentation and the software included with this product are copyrighted 2020 by Advantech Co., Ltd. All rights are reserved. Advantech Co., Ltd. also reserves the right to improve the products described in this manual at any time without notice. No part of this manual may be reproduced, copied, translated, or transmitted in any form or by any means without the prior written permission of Advantech Co., Ltd.
Page 4
Document Feedback To assist us with improving this manual, we welcome all comments and constructive criticism. Please send all feedback in writing to support@advantech.com. Packing List Before setting up the system, check that the items listed below are included and in good condition.
Page 5
Follow these simple precautions to protect yourself from harm and the products from damage. Disconnect the power supply before making any configuration changes. The sudden rush of power after connecting a jumper or installing a card may dam- age sensitive electronic components. WISE-2410 User Manual...
Mounting ....................11 3.3.1 Installation Direction..............11 Figure 3.3 WISE-2410 Installation Direction on motor....11 Figure 3.4 WISE-2410 Detail Installation Direction on motor ..11 3.3.2 Stud mount.................. 12 Figure 3.5 Stud mount ............... 12 Figure 3.6 Stud mount ............... 12 3.3.3...
Page 8
4.1.3 Binding Process Between WISE-2410 and WISE-6610 ..... 22 WISE-2410 Configuration ............... 28 4.2.1 Information Page ................ 28 4.2.2 Configuration ................29 4.2.3 IO Status..................30 4.2.4 Data Logger ................32 4.2.5 Diagnostician ................34 Get Raw Data from WISE-2410.............. 34 4.3.1...
Provide 3 axis vibration features(Velocity RMS, acceleration peak, etc.) Compliant with ISO 10816: WISE-2410 can directly provide vibration features. By simple setting, user can monitor machine motor for evaluation of vibration severity Built-in antenna, support LoRaWAN ...
Mechanical Design and Dimensions Figure 1.2 WISE-2410 Dimension Figure 1.3 LED Color Indication Behavior Turn on 2 sec when power on Status Green Turn on 1 ms when RF transmission completely Idle WISE-2410 User Manual...
Make sure you take adequate precautions when you touch the equipment. Consider using ground straps, anti-static floor coverings, etc. if you use the equipment in low humidity environments. WISE-2410 User Manual...
Power WISE-2410 is designed for two AA 3.6VDC batteries as an power source. Press the power switch on the top of chassis (see the Figure 1.3 led) and turn on WISE-2410. Note! Battery needs to order separately 1760002647-01 3.6V/2500mAh AA Cylindrical Battery (nonrecharge-...
Interface Introduction Figure 3.1 WISE-2410 Interface Introduction Tighten two chassis Turn clockwise the top chassis to locking point to tighten bottom chassis. Figure 3.2 Tighten two chassis WISE-2410 User Manual...
Applicable installation methods are briefly described in the following sections. 3.3.1 Installation Direction WISE-2410 Builds-in 3-axis vibration sensor. Please follow the following installation guide to make sure the eigenvalues from your device are correct. Figure 3.3 WISE-2410 Installation Direction on motor Figure 3.4 WISE-2410 Detail Installation Direction on motor...
Please Wrench need to hold base steel (not contact chassis) when you use Wrench to fasten WISE-2410(with stud) to hold of motor. Figure 3.6 Stud mount 3.3.3 Magnetic bases Fasten WISE-2410 and stud, and then fasten WISE-2410(with stud) and magnetic bases. Figure 3.7 Magnetic bases WISE-2410 User Manual...
3.3.4 Adhesive Mounting Pad Fasten WISE-2410 and stud, use adhesive epoxy glue(24hours) to stick on the motor surface. Figure 3.8 Adhesive Mounting Pad Battery Replacement Slowly remove top chassis Figure 3.9 Battery Replacement Step1 Unplug and remove battery pack and its connector Figure 3.10 Battery Replacement Step 2...
Page 22
Plug in new battery and make sure the anode and cathod Figure 3.11 Battery Replacement Step 3 Figure 3.12 Battery Replacement Step3 Plug in the connector of battery pack Figure 3.13 Battery Replacement Step4 WISE-2410 User Manual...
Page 23
Figure 3.14 Battery Replacement Step5 Slowing and carefully close the top chassis, and avoid the cables. Figure 3.15 Battery Replacement Step6 Note! Please be careful for inserting cables and close the top chassis. WISE-2410 User Manual...
Connect the module to your computer via the micro-USB port. Execute WISE Studio. Clicking Go to Configuration while it shows "available USB-Serial" in USB- Serial box, press Go To Configuration. Click Connect to link the WISE-2410 and the web configuration page will appear. WISE-2410 User Manual...
Page 27
Use web configuration in WISE Utility or press Open In Browser to open the web configuration in any browser (Google Chrome is recommended). Click Information to check the basic information of the module. Click Configuration to use Information, RF Module, Time&Date, Scheduling, Control, Firmware settings. WISE-2410 User Manual...
Click IO Status to check vibration and temperature data. 4.1.2 LoRaWAN gateway (WISE-6610) configuration Default ID of WISE-6610 is 192.168.1.1 Login- Username: root Password: root You can see the main page of Router; you can change IP in LAN if needed. WISE-2410 User Manual...
Page 29
Step1: Choose User Modules and LoRaWAN Gateway. You can see WISE-6610N100-A (Support NA frequency band), make sure all of these parameters are matching with the RF module setting on WISE-2410. If you want to know any items' description, you can refer WISE-6610 user manual.
A new tab will pop-up after click on Network Server (http). Account: root Password: root 4.1.3 Binding Process Between WISE-2410 and WISE-6610 This section will guide you to setup the connection between WISE-2410 and WISE- 6610. Enter the "Network Server (http)" in WISE-6610 gateway as follow. WISE-2410 User Manual...
Page 31
Note: If select "Commissioned", which means the node will use OTAA mode for connecting with a gateway. Note: If select "Active Nodes", which means the node will use ABP mode for connecting with a gateway. Click "Device" > "Activated (Nodes)" > "+ Create" WISE-2410 User Manual...
Page 32
In this demo, a WISE-2410 is used. D. NwkSKey: the network service key address of an end node. Copy-pate "Networks Session Key" from WISE-2410 "RF module" tab. E. AppSKey: the application service key of an end node. Copy-pate "Networks Session Key" from WISE-2410 "RF module" tab.
Page 33
Back to WISE-2410 configuration setting page. Click "Configuration" > "RF Module" and choose "LoRaWAN" for RF operation mode setting on WISE-2410. Create a "network server" gateway. Copy-paste the MAC address from "LoRaWAN radio" > "LoRaWAN Gateway Identifier". Then click on "submit".
Page 34
A. Click "Application Server" > "Status". Here shows the end nodes if packets are received by gateway from an end node. B. Click "Detail". The gateway will help to pre-parsing the data payload if the "App Arguments" input correctly. WISE-2410 User Manual...
Page 35
C. Users can also access into "Network Server (http)". The "Received frames" page shows the received results. The "FCnt" shows the frame sequence. If this sequence is in-continuously, means some of the packets were lost. WISE-2410 User Manual...
WISE-2410 Configuration All functions of WISE Studio for WISE-2410 is below: System Function Item Functional Description Display module name, Network status, Power status, Information Firmware version. Module Information RF related setting Date/time, time zone settings Configuration ...
Information: Device identity and location settings RF Module: RF Related Settings Binding process between WISE-2410 and WISE-6610, please go to Section 4.1 for more details. For LoRaWAN parameter description, please check the docu- ment of "lorawan_regional_parameters" from LoRaWAN Alliance website.
Scheduling: Data reports interval setting with optional weekly scheduling setting Based on application scenario, user can set scheduling of WISE-2410. – Mode: Basic/Advance – Day: Mask for Sunday ~ Saturday – Start time: 00: 00 ~ 23: 59 –...
Page 39
If the sensing target vibrate abnormally and pass through a threshold, it can send alarm to LoRa gateway. Temperature alarm – Please select Channel 3 for Temperature sensor configuration. – If the sensing target temperature raise and pass through a threshold, WISE will send alarm to a gateway. WISE-2410 User Manual...
By Channel: 0 means X-axis. 1 means Y-axis, 2 means Z-axis, 3 means Tem- perature. – By Sensor: Data from sensors, including eigenvalues, alarm trigger, sensor status and raw data. Logger Configuration: Enable or Disable the I/O log function WISE-2410 User Manual...
Page 41
– Timestamp: Local date and time (GMT) or Coordinated universal time (UTC) Query Filter – Filter Mode: User can choose No Filter Enable, Time Filter or Amount of Lat- est Data – Query result as follow WISE-2410 User Manual...
Diagnostician Display any errors detected by module. Get Raw Data from WISE-2410 For WISE-2410 series, there are two operation modes for querying vibration raw data: Standard mode and Real Time mode. Standard mode: User could query/get raw data which was previously measured and stored in WISE-2410.
If there are more than one record, use could press "Previous" or "Next" to dis- play selected record. Recordt data could be exported as CSV file. Please select file folder and press "Export as CSV" to export records. WISE-2410 User Manual...
In Real-Time operation mode, user could get real time raw data. Please check "Export as CSV" to export records before pressing "Start" button. Press "Start" button and there will be 3 charts (X, Y, Z axis) displayed in real time. Press "Stop" button to terminate data query. WISE-2410 User Manual...
1: first seg. DevEUI 10: 8 octets DevEUI – First Segment bit Set the First Segment bit to inform the server that this is the beginning of a packet with Total Length information of WISE payload data. WISE-2410 User Manual...
+x+1 and initial value 0xFF. A.1.4 Sensor data (I/O Type: 0x5) IO Type (bit 7 - 4): 0x5 Sensor Range (bit 3 - 0): (4 bit) Sensor Type 4096 - Temperature (°C) 4256 - Accelerometer 0x5 - 0xF (RFU) WISE-2410 User Manual...
Page 48
MASK (bit 4 - 0): Range: 0x0 - 0x3 Range: 0x4 Temp. Accelerometer Bit 0 Sensor Status (1 Byte) (Reserved) Bit 1 Sensor Event (2 Bytes) Sensor Event (2 Bytes) Bit 2 Sensor Value (4 Bytes) (Reserved) WISE-2410 User Manual...
Page 49
0: not occurred 0: not occurred Low Alarm Status Bit 1 1: low alarm occurred. (Reserved) 0: not occurred Bit 2 (Reserved) (Reserved) Bit 3 (Reserved) (Reserved) Bit 4 Alarm update (Reserved) Bit 5 ~ 15 (Reserved) (Reserved) WISE-2410 User Manual...
Battery low Reserved Power Source: 1 byte Power source table is shown below. Bit Order Description Power line Battery Reserved Battery voltage: 2 bytes The battery voltage with range 0 to 65.535V. Timestamp: 4 bytes WISE-2410 User Manual...
A partial of WISE Total Length Source Address Control Number Payload 0x00 (S+1)~ The last message: WHDR WPayload* WCRC byte: 1 Variable Frame Frame Sequence The rest of WISE Total Length Source Address Control Number Payload 0x00 (S+n) 0x23 WISE-2410 User Manual...