Before installing unit, determine whether any building alterations are required to run piping,
wiring and ductwork. Follow all unit dimensional drawings and refer to the submittal
engineering dimensional drawings of individual units for proper clearances.
5.1

Installation Considerations

The evaporator unit is usually mounted above the suspended ceiling in the space to be conditioned.
Ducted systems may be located in a different room. Refer to Figures 8- 10 for possible configurations.
The system may be:
• Self-contained air-cooled with centrifugal condenser fan attached to the evaporator box.
• Split system air-cooled with outdoor propeller fan condensing units.
• Self-contained chiller water, requiring connection to building chilled water loop.
• Self-contained water/glycol-cooled, requiring water or glycol loop connection.
Table 1
Application limits - evaporator and chilled water units*
Input Voltage
Minimum
-5%
* Unit will operate at these conditions but will not control to these extremes of conditions.
Table 2
Application limits - outdoor air-cooled condensing unit
Input Voltage
Minimum
-5%
Table 3
Application limits - water/glycol-cooled condenser
Input Voltage
Minimum
-5%
* Operation below 65°F (18°C) may result in reduced valve life and fluid noise.
5.1.1

Room Preparation

The room should be well insulated and must have a sealed vapor barrier. The vapor barrier in the
ceiling and walls can be a polyethylene film. Paint on concrete walls and floors should contain either
rubber or plastic.
NOTE
The vapor barrier is the single most important requirement for maintaining environmental
control in the conditioned area.
Outside or fresh air should be kept to a minimum when tight temperature and humidity control is
required. Outside air adds to the site's cooling, heating, dehumidifying and humidifying loads. Doors
should be properly sealed to minimize leaks and should not contain ventilation grilles.
NOTE
Temperature and humidity sensors are located in the wall box. Proper and efficient cooling
requires placing the wall box where discharge air does not directly blow on the sensors.
I
NSTALLATION
Range of Return Air Conditions to Unit
Maximum
Dry Bulb Temp
+10%
65 to 85°F (10 to 29°C)
Entering Dry Bulb Air Temperature
Maximum
Minimum
-30°F (34°C)
+10%
(units with Lee-Temp
receiver)
Entering Fluid Temperature
Maximum
Minimum
+10%
45°F (7°C)*
Relative Humidity
20 to 80%
Maximum
115°F (46°C)
Maximum
115°F (46°C)
15

Site Preparation and Installation

®
Liebert
Mini-Mate2