3

Technical data

General data and operating conditions

3
Technical data
3.1
General data and operating conditions
Conformity and approval
Conformity
CE
EAC
Approval
UL
CSA
GOST−R
Protection of persons and equipment
Type of protection
Earth leakage current
Insulation of control
circuits
Insulation resistance
Protective measures
EMC
Complies with requirements according to EN 61800−3
Noise emission
l
cable−guided
Noise immunity
76
2006/95/EC
Low−Voltage Directive
2004/108/EG
EMC Directive
TP TC 020/2011
Electromagnetic
compatibility of technical
(TR CU 020/2011)
means
TP TC 004/2011
On safety of low voltage
equipment
(TR CU 004/2011)
UL 508C
Underwriter Laboratories (File No. E132659)
Power Conversion Equipment
22.2 No. 14
51321.1−2000 No. POCC DE.AN30.Bo8845
51321.3−99
IEC/EN60529
IP55 without protective cap on the AIF interface,
NEMA 250 / UL50
protection against accidental contact according to type 12
IEC/EN60529
IP65 with protection cover on the AIF interface,
NEMA 250 / UL50
protection against accidental contact according to type 4
IEC/EN 61800−5−1
> 3.5 mA AC
> 10 mA DC
IEC/EN 61800−5−1
Safe mains isolation through double (reinforced) insulation
IEC/EN 61800−5−1
< 2000 m site altitude: overvoltage category III
> 2000 m site altitude: overvoltage category II
Short circuit, short to earth (protected against short to earth during operation, limited
protection against short to earth on powerup), overvoltage, motor stalling, motor
overtemperature (input for PTC or thermal contact, I
IEC/EN 61800−3
Motor mounting:
Compliance with limit class C1
Wall mounting:
– Compliance with the limit class C1 when shielded motor
cables up to a length of 1 m are used
– Compliance with the limit class C2 when shielded motor
cables up to a length of 10 m are used
Requirements
Standard
ESD
IEC/EN 61000−4−2
Cable−guided high
IEC/EN 61000−4−6
frequency
Burst
IEC/EN 61000−4−4
Surge (surge voltage
IEC/EN 61000−4−5
on mains cable)
l
Eurasian Conformity
TR CU: Technical Regulation of
Customs Union
Eurasian Conformity
TR CU: Technical Regulation of
Customs Union
Observe regulations and safety
instructions!
2
t monitoring)
Severity
8 kV with air discharge,
4 kV with contact discharge
150 kHz ... 80 MHz,
10 V/m 80 % AM (1 kHZ)
3/4, i.e. 2 kV / 5 kHz
3, i.e. 1.2 / 50 ms,
1 kV phase/phase, 2 kV phase/PE