Quick Links

Technical Data
Auxiliary switches
Feedback
Fail safe - Enerdrive
Power consumption
Control signal
Running time through
90º
Torque
Power supply
Electrical connection
Inlet bushing
Angle of rotation
Direction of rotation
Ambient temperature
Storage temperature
Relative Humidity
Weight
Warning: Do not press the clutch when actuator is powered
Dimensions
D
C
Caution
We strongly recommend that all neptronic® products be wired to a separate transformer and that transformer shall service only neptronic® products. This precaution will
prevent interference with, and/or possible damage to incompatible equipment.
When multiple actuators are wired on a single transformer, polarity must be observed. Long wiring runs create voltage drop which may affect the actuator performance.
1
Enerdrive System U.S.A. Patent #5,278,454
BBTS/050929
Feature:
• Mounts easy on round
& square shaft (with option –8).
• External clutch for manual adjustments.
• Maintenance free.
• Position indicator.
• Fail safe by Enerdrive System
(on model 1060, 1065 & 1080).
• Auxiliary switches
(on model 1021 & 1080).
BBTS1000
BBTS1005
BT000S
BT005S
No
No
No
Yes
No
6 VA
3 wire / 2 position,
3 wire / 3 point floating
2 inlet bushing of 5/8 in [15.9 mm] & 7/8 in [22.2 mm]
0 to 90 degrees, mechanically adjustable (factory set with 90º stroke)
Reversible, Clockwise (CW) or Counterclockwise (CCW) (factory set with CW direction)
A
B
Installation instruction
1
BBTS1021
BBTS1060
BT020S
BT060S
Yes (2)
No
No
No
90 - 110 sec
(Fail-safe20-30 sec)
50 in.lb. [5,6 Nm] at rated voltage
22 to 26 VAC or 28 to 32 VDC
2
18 AWG [0.8 mm
] minimum
0ºF to +122ºF [-18º C to +50º C]
-22ºF to +122ºF [-30º C to +50º C]
5 to 95 % non condensing.
3 lbs. [1.4 kg]
Dimension
A
B
C
D
Actuator
New Number
BBTS1000
BT000S
BBTS1005
BT005S
BBTS1021
BT020S
BBTS1060
BT060S
BBTS1065
BT065S
BBTS1080
BT080S
BBTS1065
BBTS1080
BT065S
BT080S
No
Yes (2)
Yes
Yes
15VA Peak, 6VA
2 wire / 2 position,
4 wire / 3 point floating
Inches
Metric (mm)
1.50
38.1
3.26
82.8
6.60
167.5
3.01
76.4
No
1

Advertisement

loading

Summary of Contents for Neptronic BBTS1000

  • Page 1 76.4 Caution We strongly recommend that all neptronic® products be wired to a separate transformer and that transformer shall service only neptronic® products. This precaution will prevent interference with, and/or possible damage to incompatible equipment. When multiple actuators are wired on a single transformer, polarity must be observed. Long wiring runs create voltage drop which may affect the actuator performance.
  • Page 2 Fix the bracket to the ductwork with #8 self-tapping screws. Wiring Diagrams Models BBTS1000, 1005 & 1021 Models BBTS1060, 1065 & 1080 3 wire / 2 position 2 wire / 2 position...

This manual is also suitable for:

Bbts1005Bbts1021Bbts1060Bbts1065Bbts1080Bt000s ... Show all