Finishing the Installation
After finishing insulating and taping over the tubing, use sealing
putty to seal off the hole in the wall to prevent rain and draft
from entering.
Apply putty here
HOW TO INSTALL THE TIMER REMOTE
CONTROLLER OR HIGH-SPEC WIRED
REMOTE CONTROLLER (OPTIONAL PART)
NOTE
See "Section 2. TEST RUN".
HOW TO INSTALL WIRELESS REMOTE
CONTROLLER (OPTIONAL PART)
NOTE
See "Section 8. HOW TO INSTALL THE WIRESS REMOTE
CONTROLLER RECEIVER".
Tubing
1-11-105
Accessories Supplied with Unit
Table 1-11-5 (Low Silhouette Ducted)
Part Name
Figure
Washer
Flare insulator
Insulating
tape
Drain
insulator
Hose band
Packing
Packing
Drain hose
Operating
Instructions
Installation
Instructions
Short-circuit
connection
Use M10 for suspension bolts.
Suspension bolts and nuts are field supply.
Type of Copper Tube and Insulation Material
If you wish to purchase these materials separately from a local
source, you will need:
1.
Deoxidized annealed copper tube for refrigerant tubing.
2.
Foamed polyethylene insulation for copper tubes as
required to precise length of tubing. Wall thickness of the
insulation should be not less than 8 mm.
3.
Use insulated copper wire for field wiring. Wire size
varies with the total length of wiring. See the section
"1-10. Electrical Wiring" for details.
CAUTION
Check local electrical codes and regulations before
obtaining wire. Also, check any specified instructions or
limitations.
Additional Materials Required for Installation
1.
Refrigeration (armored) tape
2.
Insulated staples or clamps for connecting wire (See your
local codes.)
3.
Putty
4.
Refrigeration tubing lubricant
5.
Clamps or saddles to secure refrigerant tubing
6.
Scale for weighing
Q'ty
Remarks
For suspending indoor
8
unit from ceiling
2
For gas and liquid tubes
For gas and liquid tubes
2
flare nuts
1
For drain hose joint
1
For securing drain hose
For drain hose joint
1
(hard material)
For drain hose joint
1
(soft material)
1
1
1
For high static pressure
(Located on the back of
1
the electrical component
box lid. )
1

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents