(3) Installing the panel for cassette
The power must be turned ON in order to change the
flap angle. (Do not attempt to move the flap by hand.
Doing so may damage the flap.)
1) Hang the temporary latches on the inside of the panel
for cassette to the receptacle on the unit to temporarily
attach the panel for cassette in place.
The panel for cassette must be installed in the correct
direction relative to the unit. Align the REF. PIPE and
DRAIN marks on the panel for cassette corner with
the correct positions on the unit.
When removing the panel for cassette, push the
temporary latches outward while holding the panel for
cassette.
Push to disengage.
Temporary latches (×2)
2) Align the panel installation holes and the unit screw
holes.
3) Tighten the provided washer head screws at the
4 panel installation locations so that the panel is
attached tightly to the unit.
Marking with DRAIN
Receptacle on the
main unit
Temporary latch
Drain tube corner
Refrigerant tube
corner
Panel for cassette
Marking with REF. PIPE
Washer head screws
(preinstalled on the
panel for cassette)
4) Check that the panel is attached tightly to the ceiling.
At this time, make sure that there are no gaps
between the unit and the panel for cassette, or
between the panel for cassette and the ceiling surface.
Ceiling surface
If there is a gap between the panel and the ceiling,
leave the panel for cassette attached and make fine
adjustments to the installation height of the unit to
eliminate the gap with the ceiling.
CAUTION
If the screws are not sufficiently tightened, trouble
such as that shown in the figure below may occur.
Be sure to tighten the screws securely.
Air leakage
Air leakage from
panel for cassette
Staining
If a gap remains between the ceiling surface and the
panel for cassette even after the screws are tightened,
adjust the height of the unit again.
Adjust so that there
are no gaps.
If there is no affect to the horizontal of the unit and
drain tube, adjustment to the installation height of the
unit can be made through the hole of the panel for
cassette corner.
1-11-47
Do not allow gaps.
Main unit
Panel for cassette
Make fine adjustment by a wrench or
other tools to the installation height
of the unit to eliminate the gap with
the ceiling through the holes of the
corner cover.
Condensation, water leakage
1