Checking the Drainage

CAUTION
After wiring (refer to 1-10. Electrical Wiring.) and drain
piping are completed, use the following procedure to check
that the water will drain smoothly. For this, prepare a bucket
and wiping cloth to catch and wipe up spilled water.
(1) Connect power to the power terminal board (L, N
terminals) inside the electrical component box.
(2) Slowly pour about 1 L of water into the drain pan to
check drainage.
Drainage check
Over 100 mm
Plastic container for
water intake
(3) Short the check pin (CHK) (6P : 5-6) on the indoor
control board and operate the drain pump. Check the
water flow through the transparent drain pipe and see if
there is any leakage.
* If the check pin (CHK) (6P:5-6) is shorted, the fan starts
rotating at high speed and could cause injury.
(4) When the check of drainage is complete, open the check
pin (CHK) (6P : 5-6) and remount the tube cover.
(5) Checkpoint after installation
After installation of indoor and outdoor units, panels
and electrical wiring, check the following items.
Be careful since the fan will start
when you short the pin on the
indoor control board.
Drain pan outlet
Water (Approx. 1 L)
Important Note for Wiring 4-Way Cassette Type
(1) The power supply inlet is located at the lower area of
the refrigerant tubing side of the unit. The electrical
component box is located at the air intake of the bottom
of the unit.
(2) Before installing the panel for cassette, be sure to carry
out the wiring connection.
(3) Remove the lid located on the bottom of the indoor unit
attaching the electrical component box by unscrewing
the Phillips head tapping screws (×2).
Tapping screw position
(4) Lead the wires from the power supply inlet to the unit.
Be sure to lead the wires through the power supply inlet.
Make sure that no wire is caught between the indoor unit
and panel for cassette. Otherwise, the unit may cause a
fire.
(5) Connect the wires into the terminals through the power
supply inlet for the electrical component box.
Fix the wires with a clamping clip.
(6) Reinstall the lid of the electrical component box in its
original position with paying attention not to have the
wires caught in the lid.
Refer to "1-10. Electrical Wiring".
12
1-11-34
Power supply inlet