Installation, Operation and Maintenance Manual
VCIOM-15204-EN Rev. 1
Section 10:
Figure 6
Limit
Switches
•
•
•
•
•
•
•
•
Limit Switch Setting Instructions
Limit Switch Setting Instructions
Operate the actuator manually to closed position.
Using a hex wrench, loosen the cam adjustment screw in the CLOSE limit switch cam.
Rotate the CLS cam towards CW limit switch lever until the switch 'clicks'.
Tighten set screw with hex wrench.
Operated the actuator manually to open position.
Using a hex wrench, loosen the cam adjustment screw in the OPEN limit switch cam.
Rotate the OLS can towards CCW limit switch lever until the switch 'clicks'.
Tighten set screw with hex wrench.
Section 10: Limit Switch Setting Instructions
May 2020
Close Limit
Switch Cam
Open Limit
Switch Cam
Cam Adjust-
ment Screw
11