Check code
[F13] / [43]
(Current code / AI-NET)
Sub-code: 01: Compressor 1 side 02: Compressor 2 side
This error code means IGBT built-in temperature sensor error.
Check connection of connectors CN06 on IPDU P .C. board and CN600 on I/F P .C. board.
If sensor is normal, replace IPDU P .C. board.
Check code
[F15] / [18]
(Current code / AI-NET)
Are installed positions of
TE1 sensor and TL sensor correct?
YES
Are connection of TE1 sensor connector
and TL sensor connector normal?
YES
Are resistance characteristics of
TL sensor and TE1 sensor normal?
YES
Check outdoor I/F P.C. board.
Defect → Replace
∗ TE1 sensor : Outdoor heat exchanger temp sensor
TL sensor : Temp sensor between liquid tanks of outdoor PMV1/2
Check code name
TH sensor error
Check code name
Outdoor temp sensor
miscabling (TE1, TL)
NO
Outdoor I/F P.C. board
TE1 sensor : CN505, Green
TL sensor : CN521, White
NO
NO
∗ Outdoor unit temperature sensor characteristics
See TE1 sensor : Characteristics-5
See TL sensor : Characteristics-2.
90
Cause of operation
IGBT built-in sensor error in A3-IPDU
Cause of operation
1. Misinstallation and misconnection of TE1 sensor
and TL sensor
2. Resistance characteristics error of TE1 sensor
and TL sensor
3. Outdoor P.C. board (I/F) error
Correct installed positions of
TE1 sensor and TL sensor.
Correct connection of connectors.
Correct connection of connectors.