Check code
Main
Outdoor 7-segment display
remote
controller
Check code
Sub-code
P26
P26
01: Compressor 1 side
02: Compressor 2 side
P29
P29
01: Compressor 1 side
02: Compressor 2 side
P31
Detected
AI-NET
Check code name
position
central control
remote controller
14
IPDU
G-Tr short-circuit protection
error
16
IPDU
Compressor position
detection circuit error
47
Indoor
Other indoor error
(Group follower unit error)
Status
Error detection condition
All stop
Instantaneous over-current was
detected when compressor started.
All stop
Position was not normally detected.
Corresponding
E07/L07/L03/L08 was detected
unit only stops.
when other indoor unit in the group
was defective.
Check item (position)
• Check connector connection and wiring on IPDU P .C. board.
• Check compressor error and defect of compressor coil.
• Check outdoor P .C. board (IPDU) error.
• Check connector connection and wiring.
• Check compressor error and defect of compressor coil.
• Check P .C. board (IPDU) error.
• Check indoor P .C. board.