Toshiba SUPER MMK-AP0073H (IN) Service Manual page 62

Hide thumbs Also See for SUPER MMK-AP0073H (IN):
Table of Contents

Advertisement

Check code
Main
Outdoor 7-segment display
remote
controller
Check code
Sub-code
E12
E12
01: Indoor/outdoor
communication
02: Between outdoors
communication
E15
E15
E16
E16
00: Capacity over
01 to: No. of connected units
E18
E19
E19
00: No header unit
02: Two or more header units
E20
E20
01: Connection of outdoor of
other line
02: Connection of indoor of
other line
E23
E23
Detected
AI-NET
Check code name
position
central control
remote controller
42
I/F
Automatic address start error
42
I/F
No corresponding indoor unit
during automatic address
89
I/F
No. of connected indoor units /
Capacity over
97, 99
Indoor
Communication error between
unit
indoor header and follower
units
96
I/F
Outdoor header unit quantity
error
42
I/F
Other line unit connected
during automatic address
15
I/F
Communication sending error
between outdoor units
Status
Error detection condition
All stop
• When indoor automatic address
started, other refrigerant circuit system
was setting automatic address.
• When outdoor automatic address
started, indoor automatic address was
executed.
All stop
Indoor unit is not found when indoor
automatic address start was set up.
All stop
• Total capacity of indoor units exceeded
135% of total outdoor capacity.
• No. of connected indoor units are more
than 48 units.
[Note]
If this code appears after backup setup
of outdoor unit trouble, set up "No
capacity-over detection".
<Setup method of
"No capacity-over detection">
Turn on SW09/Bit 2 on I/F P .C. board of
outdoor header unit.
Corresponding
Regular communication between indoor
unit only stops.
header and follower units .
All stop
• There are multiple outdoor header
units in 1 line.
• There is none of outdoor header unit in
1 line.
All stop
Unit of other line was connected when
indoor automatic address started.
All stop
Transmission of other outdoor unit was
unavailable for 30 seconds or more.
Check item (position)
• Setup the address again after disconnecting
communication connection with other refrigerant
circuit system.
• Check the communication line connection
between indoor and outdoor.
• Check the electric power line error in indoor.
• Check the noise of surrounding devices.
• Power failure
• Check indoor P .C. board error.
• Check the connection capacity of indoor unit.
• Check the HP capacity of indoor unit.
• Check the indoor/outdoor capacity setup
• Check the No. of connected indoor units.
• Check the outdoor I/F P .C. board error
• Check wire of the remote controller.
• Check power wiring of indoor.
• Check P .C. board of indoor.
• Check SW02 setup on the wall type P .C. board.
(Should be Bit 1: ON, Bit 2: OFF)
The outdoor unit connected with communication
wire between indoor and outdoor (U1.U2) is the
outdoor header unit.
• Check connection of communication line
between indoor and outdoor.
• Check outdoor P .C. board(I/F) error.
Separate the wire between lines according to
automatic address setup method in "Address
setup".
• Check the power of outdoor unit.
(Is the power turned on?)
• Check connection of communication wire or
disconnection between outdoor units.
• Check the connector for communication on
outdoor P .C. board.
• Check outdoor P .C. board (I/F) error.
• Check the end terminal resistance setup for
communication between outdoor units.