3
SELECTION OF INSTALLATION PLACE
n Installation diagram of Indoor and outdoor units
Before installing the
wireless remote controller
1. Remove the battery cover.
2. Insert 2 new batteries
(R03 [AAA] type) following
the (+) and (–) positions.
Wireless remote controller
Cover
Batteries
Batteries
Pan head wood screw
Wireless remote controller
Remote controller holder
n Installation space
The indoor unit shall be installed so that its top surface comes at a height of 2m or more.
Also it must be avoided to put anything on top of the indoor unit.
∗1 Reserve space required to install the indoor unit and for service work.
Keep 110mm or more for clearance between top plate of the indoor unit and the ceiling surface.
∗2 Provide a space as shown for service clearance for the cross flow fan.
n Installation place
• A place which provides the spaces around the indoor unit as shown in the above diagram.
• A place where there is no obstacle near the air inlet and outlet.
• A place that allows easy installation of the piping to the outdoor unit.
• A place which allows the front panel to be opened.
• Direct sunlight to the indoor unit' s wireless receiver should be avoided.
• The microprocessor in the indoor unit should not be too close to RF noise sources.
(For details, see the owner' s manual.)
For the rear left and left piping
Hook
Installation plate
Insert the cushion between the indoor
unit and wall, and tilt the indoor unit for
better operation.
Hook
Do not allow the drain hose to get slack.
Cut the piping hole
sloped slightly.
Make sure to run the drain hose sloped
Shield pipe
downward.
Heat
insulator
The auxiliary piping can be connected
to the left, rear left, rear right, right,
bottom right or bottom left.
Right
Rear right
Bottom right
Rear left
CAUTION
n Wireless remote controller
• A place where there are no obstacles such as a curtain that may block the signal from the indoor unit.
• Do not install the remote controller in a place exposed to direct sunlight or close to a heating source,
such as a stove.
• Keep the remote controller at least 1m
Wall
apart from the nearest TV set or stereo
equipment.
(This is necessary to prevent image
disturbances or noise interference.)
• The location of the remote controller
should be determined as shown below.
4
INSTALLATION OF INDOOR UNIT
Install the air conditioner certainly to sufficiently withstand the weight.
If the strength is insufficient, the unit may fall down resulting in human injury.
Perform a specified installation work to guard against strong wind or earthquake.
An incomplete installation can cause accidents by the units falling and dropping.
Left
Bottom left
REQUIREMENT
Strictly comply with the following rules to prevent damage of the indoor units and human injury.
• Do not put a heavy article on the indoor unit. (Even units are packaged)
• Carry in the indoor unit as it is packaged if possible. If carrying in the indoor unit unpacked by necessity, be
sure to use buffering cloth, etc. to not damage the unit.
• To move the indoor unit, do not apply force to the refrigerant pipe, drain pan, foamed parts, or resin parts, etc.
• Carry the package by two or more persons, and do not bundle it with plastic band at positions other than
specified.
Be careful to the following items when installing the unit.
• Considering air discharge direction, select an
installation place where discharge air can circulate
evenly in a room.
Avoid to install the unit at place with "NO GOOD"
mark in the right figure.
(Side view)
(Top view)
Indoor unit
Reception range
Reception range
Remote controller
Remote controller
∗ : Axial distance
WARNING
OK
NO GOOD
Bad installation place
: Not cooled well.
Good installation place
Cooled well all over.
Screen