Toshiba SUPER MMK-AP0073H (IN) Service Manual page 134

Hide thumbs Also See for SUPER MMK-AP0073H (IN):
Table of Contents

Advertisement

No.
Part name
S
<Cautions at work>
PMV motor
Using spanners by 17mm and 19mm, remove the
PMV motor. <AP0243 to AP0153>
Using spanners by 16mm and 19mm, remove the
PMV motor. <AP0123 to AP0073>
To avoid deformation of the pipes, do not use a
monkey wrench. In case that the clearance to the
ceiling is 110, use a spanner with length by 150
mm or shorter.
1) Perform work of item
2) Perform work of item
3) Remove the bundling band of PMV motor lead
wire.
4) Pull off butyl of PMV main unit until the position
shown in the right photo.
5) Using a spanner, remove PMV.
<Caution in reassembling>
Determine PMV motor lead wire drawing-out
position as same as that before removing.
Return butyl rubber to the original position.
T
Horizontal
1) Remove shaft of the horizontal louver from the
louver
back body. (First remove the left shaft, and then
remove other shafts while sliding the horizontal
louver leftward.)
Procedures
Q
.
R
.
134
Remarks
<AP0243 to AP0153>
Spanner push-in part
(Main unit side: 17 mm)
Butyl rubber
Spanner push-in part
(Motor side: 19 mm)
<AP0123 to AP0073>
Spanner push-in part
(Main unit side: 16 mm)
Butyl rubber
Spanner push-in part
(Motor side: 19 mm)
110 mm
or more

Advertisement

Table of Contents