Braeburn Premier Series Installer Manual page 9

3-zone control panel, 1 heat/1 cool conventional systems
Hide thumbs Also See for Premier Series:

Advertisement

4
Configuration
The configuration settings must be properly set in order for this zone panel to operate correctly. The Installer
Settings will automatically adjust so that settings that do not apply to this installation will be skipped.
All settings are shown below with comments.
No. Installer Setting
(
Notes follow table)
1
Fan Control
2
Zone Fan Purge Time
3
Supply Air Sensor Control
4
Temperature Scale*
5
Plenum High Limit Cutout
6
Plenum Low Limit Cutout
7
Short Cycle Protection
8
Second Stage Fan
9
Priority Zone
10
Opposite Mode Timer
*Note: Changing #4 will reset settings 5 and 6.
NOTES - Configuration
[1] Disable will not show plenum temperature.
[2] Only available if optional supply air sensor is connected (Model 149156)
[3] Only available if supply air sensor is enabled.
Display
Factory
Indicator
Default
FAN 1
GAS
PURGE
90
SA SENS
NO
DEG
DEG F
PLENUM
135
(
60˚C)
SET HI LIMIT
PLENUM
45
SET LO LIMIT
(8˚C)
SCP
5
G2 ZONES
2
PRIORTY
OFF
OP MODE
15
Setting
Comments
Options
(More information follows this table)
GAS
Select for 1st Stage fan controlled by equipment
EL
Select for 1st Stage fan controlled by panel
300
Select for 300 second purge into calling zone at call end
240
Select for 240 second purge into calling zone at call end
180
Select for 180 second purge into calling zone at call end
120
Select for 120 second purge into calling zone at call end
90
Select for 90 second purge into calling zone at call end
60
Select for 60 second purge into calling zone at call end
30
Select for 30 second purge into calling zone at call end
0
Select for no purge into calling zone at call end
YES
Select for Active Supply Air Sensor
NO
Select for Inactive Supply Air Sensor [Note 1, 2]
DEG F
Select for Fahrenheit display
DEG C
Select for Celsius display
100 to 180
Select the maximum Supply Air Temperature the system
(
40
to
80˚C
) can reach before shutting off all heating stages [Note 2, 3]
30 to 60
Select the minimum Supply Air Temperature the system
(
0˚C
to
15˚C
) can reach before shutting off all cooling stages [Note 2, 3]
5 to 0
Selects a compressor short cycle protection delay of 5,
4, 3, 2, 1 or zero minutes after a compressor call
2, 3
Select the number of zones that must call before the
second stage fan will turn on
OFF
Select to have opposite calls answered in any zone
1 to 3
Select zone 1 to 3 to limit calls so equipment will only
service call matching last call of zone 1-3
15 to 60
Select the number of minutes to delay system changeover
when zones are calling for heat and others zones are
calling for cooling
9