Wiring - Braeburn Premier Series Installer Manual

3-zone control panel, 1 heat/1 cool conventional systems
Hide thumbs Also See for Premier Series:

Advertisement

3.1
Damper Wiring
Always turn off power to the heating/air conditioning system prior to installing or adjusting the zone panel. Wire
the entire panel before applying transformer power.
Use the following general wiring instructions for all systems. Specific wiring will vary depending on the equipment
and type of system (conventional or heat pump).
Install the system dampers using the instructions provided by the manufacturer. Connect the dampers to the zone
panel as shown for either a 2-wire or 3-wire damper. The sum of all dampers powered by the zone panel should
not exceed 100 VA at 24 VAC. Use a slave relay if additional damper power is required.
ALWAYS PROVIDE DISCONNECT AND OVERLOAD PROTECTION AS REQUIRED
Max. damper VA per Zone 50 VA @ 24 VAC
PO
COM
PC
Zone Panel
2-Wire PC/SR Damper
3.2
Thermostat Wiring
Install the system thermostats using the instructions provided by the manufacturer. Connect the thermostats
to the zone panel as shown.
ALWAYS PROVIDE DISCONNECT AND OVERLOAD PROTECTION AS REQUIRED
CONVENTIONAL THERMOSTATS
1 HEAT / 1 COOL
R
24 VAC Power
W
Heat Call
Y
Cooling Call
G
Fan Call
C
24 VAC Transformer Common
[Note 1]
PO
COM
PC
Zone Panel
2-Wire PO/SR Damper
NOTES
[1] Wiring to the C terminal is required
only for thermostat power.