Figure E-3: Unimode 400 External Adt-Udact Mounting In Adt-Abs8Rf - ADT -UDACT Product Information

Adt digital alarm communicator transmitter installation operation manual
Table of Contents

Advertisement

Install 120 watt EOL
resistor (PN: 71244) on
TB1 terminals 3 and 4 if
last or only device on
EIA-485 line
Supervised and
Power-limited
EIA-485 and
power wiring
Notes:
1) Ferrite cores are recommended for all applications.
2) Recommended wire is 12 AWG to 18 AWG twisted pair.
3) Shielded wire is not required (unless mandated by local AHJ).
If shielded wire is used, connect only one end of shield:
a) shield may be connected to cabinet (earth ground) at fire alarm panel, or
b) shield may be connected to TB1 Terminal 5 (Shield) at ADT-UDACT as shown in Figure E-3.
NOTE: The shield end that is not connected should be insulated to prevent accidental grounding.
Do not connect both ends of shield under any circumstance since a ground fault may result.
4) Conduit is recommended for external wire runs. Consult local building codes.
5) Connect Ground Strap (supplied with ADT-ABS8RF enclosure) from Earth Ground terminal on ADT-
UDACT to a solid building earth ground. Conduit alone will not provide a reliable earth ground.
6) ADT-UDACT may be located up to 6,000 feet away from the host control panel.
7) Refer to Specifications for power requirements.

Figure E-3: Unimode 400 External ADT-UDACT Mounting in ADT-ABS8RF

60
Unimode 400 Cabinet
ADT-CPU-400
EIA-485 (ACS Mode)
TB4-1 (+)
TB4-2 (–)
MPS-400
TB2-1 (+)
TB2-2 (–)
24 VDC
Nonresettable
power
DO NOT USE
Document 50934
Rev B
5/15/00
PN 50934:B
Ferrite cores
PN 29090
To supervised
phone lines
ADT-UDACT in ADT-ABS8RF
(shown with cover removed)
Solid earth
ground