4+2 Standard and 4+2 Express Formats
I
f '1, A or C' are entered for address 42, the following is automatically programmed
for the Secondary phone number event codes. Enter a '0' for the data setting to disable
the report. These formats do not support zone/point programming. For zone/point
reporting, refer to Contact ID.
Address
Description
139 - 140
Secondary # General Alarm Code
141 - 142
Secondary # Zone/Point Alarm Code
143 - 144
Secondary # General Supervisory Code
145 - 146
Secondary # Zone/Point Supervisory Code
147 - 148
Secondary # General Fault Code
149 - 150
Secondary # AC Fault Code
151 - 152
Secondary # Zone/Point Fault Code
153 - 154
Secondary # Low Battery Fault Code
155 - 156
Secondary # Telco Primary Line Fault Code
157 - 158
Secondary # Telco Secondary Line Fault Code
159 - 160
Secondary # NAC Fault Code
161 - 162
Secondary # Comm. Trouble Primary Number Code
163 - 164
Secondary # Comm. Trouble Secondary Number Code
165 - 166
Secondary # 485 Comm. Trouble Code
167 - 168
Secondary # System Off Normal Code
169 - 170
Secondary # ADT-UDACT Off Normal Code
171 - 172
Secondary # General Alarm Restore Code
173 - 174
Secondary # Zone/Point Alarm Restore Code
175 - 176
Secondary # General Supervisory Restore Code
177 - 178
Secondary # Zone/Point Supervisory Restore Code
179 - 180
Secondary # General Fault Restore Code
181 - 182
Secondary # AC Fault Restore Code
183 - 184
Secondary # Zone/Point Fault Restore Code
185 - 186
Secondary # Low Battery Fault Restore Code
187 - 188
Secondary # Telco Primary Line Fault Restore Code
189 - 190
Secondary # Telco Secondary Line Fault Restore Code
191 - 192
Secondary # NAC Fault Restore Code
193 - 194
Secondary # Comm. Trouble Primary # Restore Code
195 - 196
Secondary # Comm. Trouble Secondary # Restore Code EE
197 - 198
Secondary # 485 Comm. Trouble Restore Code
199 - 200
Secondary # System Off Normal Restore Code
201 - 202
Secondary # ADT-UDACT Off Normal Restore Code
203 - 204
Secondary # System 24 Hour Test
205 - 206
Secondary # System 24 Hour Test w/active events
207 - 208
Secondary # Manual Test
Note:
Zero entries prevent the transmission of the report to the Central Station.

Table 3-6: Event Codes, Secondary Number

Document 50934
Rev B
5/15/00
PN 50934:B
Setting
11
00
81
00
F1
F6
00
F8
FA
FB
FC
FD
FE
FE
FF
FF
E1
00
E2
00
E3
E6
00
E8
EA
EB
EC
ED
EE
EF
EF
99
91
92

Hide quick links: