Table 3-4: Ademco Contact Id, Primary Number - ADT -UDACT Product Information

Adt digital alarm communicator transmitter installation operation manual
Table of Contents

Advertisement

Ademco Contact ID Format
If 'E' is entered for address 16, the following data is automatically programmed for the Primary
phone number event codes.
Address
69 - 71
72 - 74
75 - 77
78 - 80
81 - 83
84 - 86
87 - 89
90 - 92
93 - 95
96 - 98
99 - 101
102 - 104
105 - 107
108 - 110
111 - 113
114 - 116
117 - 119
120 - 122
123 - 125
Notes:
26
Enter a '000' for the data setting to disable the report.
Description
Primary # General Alarm Code
Primary # Zone/Point Alarm Code
Primary # General Supervisory Code
Primary # Zone/Point Supervisory Code
Primary # General Fault Code
Primary # AC Fault Code
Primary # Zone/Point Fault Code
Primary # Low Battery Fault Code
Primary # Telco Primary Line Fault Code
Primary # Telco Secondary Line Fault Code
Primary # NAC Fault Code
Primary # Comm. Trouble Primary # Code
Primary # Comm. Trouble Secondary # Code
Primary # 485 Comm. Trouble Code
Primary # System Off Normal Code
Primary # ADT-UDACT Off Normal Code
Primary# System 24 Hour Test
Primary # System 24 Hour Test w/active event 608
Primary # Manual Test Message
1) Note: Zero entries prevent the transmission of the report to the Central Station.
2) Refer to Contact ID program locations 64 - 68.
3) The identification of the zone/device number is automatically transmitted by the ADT-UDACT and is
added to the main event code. See Table 5-3 for more information.
4) For control panels Unimode 2020/1010, ADT-MNNA, and the Unimode 300/400 the factory default
event code is 110 and reprogrammable. The Unimode 400 is unique in point reporting mode in that
only the control module report codes are programmable. The factory setting of report code 111 is
fixed for addressable smoke detectors and cannot be changed.
5) The Group # is automatically incremented for Unimode 2020/1010 and ADT-MNNA applications.

Table 3-4: Ademco Contact ID, Primary Number

Document 50934
5
5
5
Rev B
5/15/00
PN 50934:B
Setting
1
Group #
6
Sensor No.
110
00
4
110
00
200
00
200
00
300
00
301
00
380
00
302
00
351
00
352
00
321
00
354
00
354
00
300
00
308
00
350
00
602
00
00
601
00
000
2
3
Note
2
000
3
Note
3
Note