2.4.3
Connection of the high power factor converter (FR-HC2)
When connecting the high power factor converter (FR-HC2) to suppress power harmonics, perform wiring securely as follows. Incorrect connection will damage
the high power factor converter and the inverter.
After making sure that the wiring is correct and secure, set the rated motor voltage in Pr.19 Base frequency voltage (under V/F control) or Pr.83 Rated motor
voltage (under other than V/F control) and "2 or 102" in Pr.30 Regenerative function selection. (Refer to the FR-A800 Instruction Manual (Detailed).)
MCCB
MC
Three-phase
AC power
supply

Remove jumpers across terminals R/L1 and R1/L11 as well as across terminals S/L2 and S1/L21, and connect the power supply for the control circuit to terminals R1/
L11 and S1/L21. Do not connect anything to power input terminals (R/L1, S/L2, and T/L3). Incorrect connection will damage the inverter. (The E.OPT fault (Option fault)
occurs. (Refer to the FR-A800 Instruction Manual (Detailed).)

Do not install an MCCB across terminals P/+ and N/- (between terminals P and P/+ or between terminals N and N/-). Connecting the opposite polarity of terminals N/-
and P/+ will damage the inverter.

Use Pr.178 to Pr.189 (Input terminal function selection) to assign the terminals used for the X10 (X11) signal. (Refer to the FR-A800 Instruction Manual (Detailed).)
For RS-485 or any other communication where the start command is only transmitted once, use the X11 signal to save the operation mode at the time of an
instantaneous power failure.

Assign the IPF signal to a terminal on the FR-HC2. (Refer to the Instruction Manual of the FR-HC2.)

Always connect terminal RDY on the FR-HC2 to a terminal where the X10 signal or MRS signal is assigned on the inverter. Always connect terminal SE on the FR-HC2
to terminal SD on the inverter. Not connecting these terminals may damage the FR-HC2.

Always connect terminals R/L1, S/L2, and T/L3 on the FR-HC2 to the power supply. Operating the inverter without connecting them will damage the FR-HC2.

Do not install an MCCB or MC across terminals (R/L1, S/L2, T/L3) on the reactor 1 and terminals (R4/L14, S4/L24, T4/L34) on the FR-HC2. Doing so disrupts proper
operation.

Securely perform grounding (earthing) by using the grounding (earthing) terminal.

Installation of a fuse is recommended. (Refer to the Instruction Manual of the FR-HC2.)

Outside box is not available for the FR-HC2-H280K or higher. Connect filter capacitors, inrush current limit resistors, and magnetic contactors. (Refer to the Instruction
Manual of the FR-HC2.)
NOTE
• The voltage phases of terminals R/L1, S/L2, and T/L3 and the voltage phases of terminals R4/L14, S4/L24, and T4/L34 must be matched.
• The control logic (sink logic/source logic) of the high power factor converter and the inverter must be matched. (Refer to the FR-A800 Instruction Manual (Detailed).)
Outside box
Reactor1
Reactor2

(FR-HCB2)
(FR-HCL21)
(FR-HCL22)



R3/
R2/
R3/
R/
R2/
L13
L12
L1
L13
L12
S3/
S/
S2/
S2/
S3/
L23
L22
L2
L23
L22
T3/
T2/
T3/
T/
T2/
L33
L3
L32
L32
L33

ROH1
ROH2
88R
88S

Connection of stand-alone option units
High power
factor converter
(FR-HC2)

R4/
R4/L14
L14
S4/
S4/L24
L24
T4/
T4/L34
L34


Fuse
P/+
ROH
N/-
SD
88R

RDY
88S

IPF
R/L1
S/L2

RSO
T/L3
SE
R1/L11
S1/L21

Inverter

Motor
R/L1
U
S/L2
V
M
T/L3
W
R1/L11
S1/L21
Earth
(ground)
P/+

N/-


X10
X11

RES
SD

23
WIRING