Application Guidelines Scroll compression principle In a Danfoss SH scroll compressor, the compression is performed by two scroll elements located in the upper part of the compressor. Suction gas enters the compressor at the suction connection. As all of the gas flows around and...
Application Guidelines Features SH range is composed of SH090-105-120-140- • Gas intake design induces higher resistance to 161-184 (light commercial platform) and SH180- liquid slugging. 240-295-380-485 (large commercial platform). The SH485 compressors include additional The SH090-105-120-140-161-184 compressors features for enhanced protection and efficiency: benefit from a further improved design to •...
Application Guidelines Compressor model designation Danfoss SH scroll compressors for R410A are Code numbers for ordering are listed section available as single compressors. The example “Ordering information and packaging”. below presents the compressor nomenclature which equals the technical reference as shown on For tandem and trio assemblies, please refer the compressor nameplate.
Subject to modification without prior notification. Data given for motor code 4 compressor, for full data details and capacity tables refer to Online Datasheet Generator: www.danfoss.com/odsg * SH295 replaces SH300. SH300 model remains available for after-market, please refer to datasheets for technical details.
2"1/4 - 1"5/8 sleeve. connection This connection must be used to mount an oil and gauge port equalisation line when two or more compressors are mounted in parallel (please refer to Danfoss SH Parallel Application Guide lines FRCC.EC.008. for details). Oil drain connection...
Application Guidelines Electrical data, connections and wiring Motor voltage Danfoss SH scroll compressors are available in five different motor voltages as listed below. Motor voltage code Code 3 Code 4 Code 6 Code 7 Code 9 380-400V - 3 ph...
Any compressor damage related to this installed in an enclosure, precautions must be will not be covered by Danfoss warranty. In the taken to avoid that the temperature around the same manner, cables must be selected in a way...
25°C, the measured resistance must be corrected using following formula: Danfoss MCI soft-start The inrush current for the Danfoss SH scroll starting current of 3-phase AC motors; they controller compressors with motor code 4 (400V /3ph...
Application Guidelines Electrical data, connections and wiring MCI with by-pass contactor By means of the built-in auxiliary contact (23-24) the by-pass function is easily achieved, see wiring diagram beside. No heat is generated from the MCI. As the contactor always switches in no-load condition it can be selected on the basis of the thermal current (AC-1).
Page 19
Application Guidelines Electrical data, connections and wiring Compressor model SH180-240-295-380 Wiring diagram with pump-down cycle Wiring diagram without pump-down cycle Compressor model SH485 Wiring diagram without pump-down cycle Wiring diagram with pump-down cycle Legend Fuses ....................F1 Liquid Line Solenoid valve ............LLSV Compressor contactor ..............
Internal reverse vent SH240 - 295 - 380-485 Electronic module located in terminal box Compressor models SH090-105-120-140-161-184 While not compulsory, an additional external have been provided with an internal overload overload is still advisable for either alarm or motor protection to prevent against excessive manual reset.
Application Guidelines Electrical data, connections and wiring Compressor models SH090-105-120-140-161-184, the bearings. Reverse rotation will be obvious incorporate an internal reverse vent valve which to the user as soon as power is turned on: the will react when the compressor is run in reverse...
• Refrigerant cost • Compressor capacity and efficiency • Refrigerant availability Danfoss Commercial Compressors, along with and use in coming years, in accordance with the the whole refrigeration and air conditioning international Montreal Protocol (1984). industry, shares today’s concern about the...
SH compressors can be applied from -35°C to designed as 100% suction gas cooled without temperature 55°C ambient temperature for SH090-105-120- need for additional fan cooling. Ambient 140-161-184 and 51°C ambient temperature for temperature has very little effect on the SH180-240-295-380-485.
Insulation output relay to trip. Bracket For SH090 to 380, DGT protection is required if The discharge gas thermostat accessory kit (code the high and low pressure switch settings do 7750009) includes all components required for not protect the compressor against operations installation as shown above.
R410A. operated full time under such condition. Cycle rate limit Danfoss recommends a restart delay timer to There must be no more than 12 starts per hour, a limit compressor cycling. The timer prevents number higher than 12 reduces the service life of reverse compressor rotation, which may occur the motor-compressor unit.
Application Guidelines System design recommendations General Successful application of scroll compressors beyond the limits given in this manual. Poor is dependent on careful selection of the performance, reduced reliability, or both may compressor for the application. If the compressor result. is not correct for the system, it will operate Essential piping design The working pressure in systems with R410A is...
Refrigerant charge limit Danfoss SH compressors can tolerate liquid Use the tables below to quickly evaluate the refrigerant up to a certain extent without major required compressor protection in relation with problems.
Note: for special conditions such as low ambient temperature, low refrigerant load or brazed plate heat exchangers please refer to corresponding sections. More detailed information can be found in the paragraphs hereafter. Please contact Danfoss Technical Support for any deviation from these guidelines. Off-cycle migration Off-cycle refrigerant migration is likely to occur...
Page 30
In certain conditions, the discharge valve in the the refrigerant charge into the condenser and SH090 - 105 - 120 - 140 - 161 - 184 compressor receiver before the system stops on the low may not completely seal and result in compressor pressure pump-down switch.
A continuous liquid flood back will cause oil dilution and, in extreme situations, lead to lack Danfoss SH scroll compressors can tolerate of lubrication and high rate of oil leaving the occasional liquid flood back. However, system compressor.
“Low pressure” in order to prevent this from happening. Low ambient operations The Danfoss SH scroll compressor requires a The superheat setting of the expansion device minimum pressure differential between the should be sufficient to ensure proper superheat suction and discharge pressures (please refer levels during low loading periods.
Application Guidelines Specific application recommendations Sump heaters Sump heaters are strongly recommended on will minimize refrigerant migration caused by all systems where the compressor is exposed to the large temperature gradient between the low ambient temperatures, especially split and compressor and the remainder of the system, remote condenser installations.
Page 34
135°C. be installed on the discharge line to protect Discharge line, reversing The Danfoss SH scroll compressor is a high position. At the same time, it is important that valve, solenoid valves volumetric machine and, as such, can rapidly...
Application Guidelines Specific application recommendations Suction line accumulator The use of a suction line accumulator is strongly Sustained and repeated liquid slugging and recommended in reversible-cycle applications. flood back can seriously impair the oil’s ability This because of the possibility of a substantial to lubricate the compressor bearings.
Sound power and attenuation are given at ARI conditions, measured in free space Data given for motor code 4 compressor, for full data details refer to online datasheet generator: www.danfoss.com/odsg * For SH140 code 3 and SH161 code 3 use acoustic hood reference 120Z0135 ** For SH380 code 3 use acoustic hood reference 120Z0579 ...
Page 37
Sound and vibration management Compressor sound radiation For sound radiating from the compressor, the Due to the unique Danfoss design of a full- emission path is airborne and the sound waves suction gas-cooled motor, compressor body are travelling directly from the machine in all insulation across its entire operating range directions.
Instructions for installation. These instructions http://instructions.cc.danfoss.com can also be downloaded from our website: Compressor handling and Each Danfoss SH scroll compressor is equipped When the compressor is mounted as part storage with two lift rings on the top shell. Always use of an installation, never use the lift rings on the both these rings when lifting the compressor.
Application Guidelines Installation Mounting of SH180-240-295- Compressors SH180-240-295-380-485 come between the flat washer and the steel mounting 380-485 delivered with rigid mounting spacers for parallel sleeve is established. The grommets attenuate mounting. to a great extent the transmission of compressor vibrations to the base frame.
5% silver or more with a melting Dissimilar metals When manipulating dissimilar metals such as Please contact Danfoss Technical support for any connection copper and brass or steel, the use of silver solder deviation from this guidelines.
34.3 bar (g) for SH180 to 485 Maximum compressor test pressure (low side) 36.7 bar (g) for SH090 to 184 Maximum compressor test pressure (high side) 48.7 bar (g) Maximum pressure difference between high and low...
50 ppm end point dryness (EPD). After burn out, remove and replace the liquid line filter drier and install a Danfoss type DAS burn- For new installations with SH compressors with out drier of the appropriate capacity. Refer to the...
(in weight) can be used to roughly define refrigerant in the oil. the required oil top-up quantity but in any case Always use original Danfoss POE oil 160SZ from the oil charge has to be adjusted based on the oil new cans.
Application Guidelines Ordering information and packaging Ordering information Danfoss SH scroll compressors can be ordered in Compressors SH180 to 485 with rigid mounting either industrial packs or in single packs. Please spacers are dedicated for parallel mounting. For use the code numbers from below tables for use in single applications the rigid spacers must ordering.
Page 49
48W 575V surface sump heater CE and UL Single pack Discharge temperature protection Type Code No Description Application Packaging Pack Size 7750009 Discharge thermostat kit SH090 to SH380 Multipack 7973008 Discharge thermostat kit SH090 to SH380 Industry pack Mounting hardware Type Code No Description Application...
Page 50
Sight glass with gaskets (black and white) All models Multipack 8156129 Gasket for oil sight glass, 1"1/8 (white teflon) All models Multipack 7956005 Gasket for oil sight glass, 1"1/8 (white teflon) All models Multipack 8154001 Danfoss Commercial Compressors blue spray paint All models Single pack AB243586442172en-001301...
Page 51
Application Guidelines Updates Previous Version Current Version • Page 14: Motor voltage • Page 14: Updated Motor voltage • Page 22: Pressure equipment directive • Page 22: Updated Pressure equipment directive 2014/68/EU 2014/68/EU • Page 41: System pressure test • Page 41: Updated System pressure test AB243586442172en-001301...