Danfoss Performer SM Series Instructions
Hide thumbs Also See for Performer SM Series:

Advertisement

Quick Links

sm / sy / sz / sh compressors
sm 084 - 185
sh
sz 084 - 185
sz 084 - 185
The compressor must only be used for its
designed purpose(s) and within its scope of
application (refer to «operating limits»).
Consult Application guidelines and da-
tasheet available from cc.danfoss.com
1
InstructIons
A: Model
B: Serial Number
c: Internal Protection
D: Supply voltage
e: Maximum operating current
F: PED Involved side (Low pressure side)
G: Lubricant
h: Refrigerant
I:
Locked rotor current
J:
Ps : Maximum Operating Pressure
K: Ts max : Maximum Operating Temperature
Ts min : Minimum Operating Temperature
L:
Manufacturing year
Installation and servicing of the
compressor by qualified personnel
only. Follow these instructions and sound
refrigeration engineering practice relating to
installation, commissioning, maintenance and
service.
T
(°C)
0
T
(°C)
0
T
(°C)
0
t
(°c)
0
Under all circumstances, the
EN378 (or other applicable local
safety regulation) requirements
must be fulfilled.
FRCC.EI.003.A1.02 © Danfoss Commercial Compressors 03/08
A
B
C
D
E
F
G
H
sy 240, 300, 380
T
(°C)
0
sz 084 - 185
T
(°C)
0
sz 240, 300, 380
T
(°C)
0
sz 240, 300, 380
T
(°C)
0
The compressor is delivered under
nitrogen gas pressure (between 0.3
and 0.7 bar) and hence cannot be
connected as is; refer to the «assem-
bly» section for further details.
I
J
K
L
The compressor must be
handled with caution in the
vertical position (maximum
offset from the vertical : 15°)

Advertisement

loading
Need help?

Need help?

Do you have a question about the Performer SM Series and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Danfoss Performer SM Series

  • Page 1 (refer to «operating limits»). safety regulation) requirements connected as is; refer to the «assem- offset from the vertical : 15°) Consult Application guidelines and da- must be fulfilled. bly» section for further details. tasheet available from cc.danfoss.com FRCC.EI.003.A1.02 © Danfoss Commercial Compressors 03/08...
  • Page 2 240 - 300 - 380 sy 240 - 300 - 380 sz 240 - 300 - 380 These Performer® compressors motors are protected by an ex- ternal module protecting against phase loss/reversal, over heating and high current draw. FRCC.EI.003.A1.02 © Danfoss Commercial Compressors 03/08...
  • Page 3 LP side. Never let the pres- correctly in one rotation direction. Line pha- sure on LP side exceed the pressure on HP side ses L1, L2, L3 must absolutely be connected FRCC.EI.003.A1.02 © Danfoss Commercial Compressors 03/08...
  • Page 4 The com- • A low-pressure switch is recommended to pressor must be operating during this process. FRCC.EI.003.A1.02 © Danfoss Commercial Compressors 03/08...