Akytec MK210-302 User Manual

Digital i/o module
Hide thumbs Also See for MK210-302:

Advertisement

Quick Links

MK210-302/312
Digital I/O module
User guide
MK210-302/312_3-EN-38929-2.4
© All rights reserved
Subject to technical changes and misprints
akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the MK210-302 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Akytec MK210-302

  • Page 1 MK210-302/312 Digital I/O module User guide MK210-302/312_3-EN-38929-2.4 © All rights reserved Subject to technical changes and misprints akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 2: Table Of Contents

    4.12. SNMP protocol ......................18 4.12.1. Basics ......................18 4.12.2. Implementation ....................19 4.13. Password .........................19 5. Installation .........................20 5.1. Mounting........................20 5.2. Wiring ........................20 akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 3 Appendix A. Dimensions .......................29 Appendix B. Galvanic isolation ....................30 Appendix C. Battery replacement ..................31 Appendix D. Modbus application ...................32 akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 4: Introduction

    Ensure the mains voltage matches the voltage marked on the nameplate. Ensure the device is provided with its own power supply line and electric fuse. akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 5 To avoid damage to the device, keep the device in the warm environment for at least 1 hour before powering on. akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 6: Overview

    Plug-in terminal blocks enable quick and easy replacement of the device. Fig. 2.1 Front view (closed cover) Fig. 2.2 Front view (open cover) akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 7 HIGH on the input (12) Output relay off green Off Output Output relay on LEDs (4) Fault status (only MK210-312) akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 8: Specifications

    File size, max. 2 kB Number of log files, ,max. 1000 Logging interval, min. 10 s Real time clock akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 9: Operating Conditions

    IP code IP20 Vibration / shock resistance conforms to IEC 61131-2 EMC emission / immunity conforms to IEC 61131-2 akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 10: Configuration And Operation

    2. Connect the power cable to the removable 2-terminal block and plug it into the device. 3. Power on the device. akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 11: Real Time Clock

    3. Set the parameter Apply new time = 0 and hold the value for at least 1 second. The time value cannot be changed more than once per second. akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 12: Battery

    If you need to assign IP addresses for several modules, it is more comfortable to use service buttons on devices (Fig. 2.2. Pos. 7), previously having all the modules connected to the PC over Ethernet. akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 13: Modbus Slave

    For details on function usage see Modbus specifications. akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 14: Digital Inputs

    If the counter overflows, the value is reset. To force a counter reset, write 0 to input value reset register. The counter will be reset within 10 ms after writing the value 0. akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 15: Frequency And Period Measurement

    Safe state can be specified in the parameter Safe state for each output. Safe state is inactive if the parameter Safe state timeout is set to 0. akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 16: Output Diagnostic (Only Mk210-311)

    (Sect. 4.8.1) Pulse counter Counter value (Sect. 4.8.2) — 0…4294967295 value Pulse counter Force counter reset On / Off reset akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 17: Debounce Filter

    Broker is a server that receives all messages from the clients and then routes the messages to the appropriate destination clients. Client can be publisher or / and subscriber. akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 18: Implementation

    QoS2 QoS2 - exactly once Keep Alive Keep Alive interval in seconds 0…600 — — Status Broker connection status akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 19: Snmp Protocol

    Each agent parameter has a unique identifier (OID – object identifier), which is a sequence of numbers separated by periods. akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 20: Implementation

    There is no password by default. If you forgot the password, restore the factory settings (Sect. 6). akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 21: Installation

    – Signal cables should be routed separately or screened from the supply cables. – Shielded cable should be used for the signal lines. akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 22: Terminal Block Layout

    Common input power supply point Not connected DO1A…DO4A, DO1B…DO4B Output terminal NOTICE Do not connect any wires to NC terminals. akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 23: Digital Inputs

    Fig. 5.6 3-wire sensor with NPN output Fig. 5.7 AB encoder with PNP output Fig. 5.8 AB encoder with NPN output akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 24: Digital Outputs

    – If the module fails (device error or power supply loss), the data is transferred directly from connector 1 to connector 2 (auto-bypass). akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 25 5 Installation Fig. 5.11 Chain topology akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 26: Factory Settings Restoration

    3. Using a thin tool, press and hold the service button (Fig. 2.2. Pos. 7) for at least 12 seconds 4. Close the cover The device will operate with the default parameters. akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 27: Maintenance

    The device should be cleaned with a damp cloth only. No abrasives or solvent- containing cleaners may be used. akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 28: Transportation And Storage

    Check the device for transport damage and completeness! Report the transport damage immediately to the shipper and akYtec GmbH. akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 29: Scope Of Delivery

    9 Scope of delivery – MK210-302/312 – Ethernet connection cable – 2-pole plug-in terminal block – Rubber plug – Short guide akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 30: Appendix A. Dimensions

    Appendix A. Dimensions Appendix A. Dimensions Fig. A.1 External dimensions Fig. A.2 Wall mounting dimensions akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 31: Appendix B. Galvanic Isolation

    Appendix B. Galvanic isolation Appendix B. Galvanic isolation Fig. B.1 Galvanic isolation akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 32: Appendix C. Battery Replacement

    The replacement should not take longer than one minute. Otherwise, the real-time clock has to be adjusted anew. Fig. C.1 Battery replacement akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 33: Appendix D. Modbus Application

    Voltage 0…3300 0x0321 UINT16 Modbus Slave Safe state timeout 0…60 0x02BC UINT8 Data logging UINT16 Logging interval 10…3600 0x0384 akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 34 DO8 PWM period 1000…60000 0x0137 UINT16 DO1 PWM duty cycle 0…1000 ‰ 0x0154 UINT16 … … … … … … … akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 35 5123 UINT16 0 – SNMPv1 — SNMP version 0x1404 5124 UINT16 1 – SNMPv2 * – Only for MK210-312 akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 36 – INT, UINT, max. 2 bytes – enumerated – REAL16 Nonexistent parameter requested Parameter value is beyond the valid limits Nonexistent parameter requested akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 37 Failed to open the file for writing Nonexistent file requested Read-only file requested Failed to write the required number of bytes akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...

This manual is also suitable for:

Mk210-312

Table of Contents