6-2. Models: AOUG36LMAS1 and AOUG48LMAS1
NOTE: Values mentioned in the table are calculated based on the maximum capacity.
COOLING
Indoor unit is higher
than outdoor unit *1
Indoor unit is lower
than outdoor unit *2
HEATING
Indoor unit is higher
than outdoor unit *1
Indoor unit is lower
than outdoor unit *2
6-2. Models: AOUG36LMAS1 and AOUG48LMAS1
m
5
7.5
ft
16
24
30
98
—
—
20
65
—
—
10
32
—
—
7.5
24
—
0.993 0.993 0.950 0.908 0.865 0.824 0.782 0.740
5
16
0.995 0.995 0.995 0.952 0.910 0.867 0.825 0.779 0.736
0
0
1.000 1.000 1.000 0.957 0.915 0.872 0.830 0.784 0.741
-5
-16
1.000 1.000 1.000 0.957 0.915 0.872 0.830 0.784 0.741
-7.5
-24
—
1.000 1.000 0.957 0.915 0.872 0.830 0.784 0.741
-10
-32
—
-20
-65
—
—
-30
-98
—
—
m
5
7.5
ft
16
24
30
98
—
—
20
65
—
—
10
32
—
—
7.5
24
—
1.000 1.000 0.998 0.995 0.993 0.990 0.853 0.828
5
16
1.000 1.000 1.000 0.998 0.995 0.993 0.990 0.853 0.828
0
0
1.000 1.000 1.000 0.998 0.995 0.993 0.990 0.853 0.828
-5
-16
1.000 1.000 0.995 0.993 0.990 0.988 0.985 0.848 0.823
-7.5
-24
—
1.000 0.992 0.990 0.987 0.985 0.982 0.845 0.820
-10
-32
—
—
-20
-65
—
—
-30
-98
—
—
- 82 -
Pipe length
10
20
30
40
32
65
98
131
—
—
0.885 0.842 0.800 0.754 0.711
—
0.937 0.895 0.852 0.810 0.770 0.728
0.990 0.947 0.905 0.862 0.822 0.780 0.738
1.000 0.957 0.915 0.872 0.830 0.784 0.741
—
0.957 0.915 0.872 0.830 0.784 0.741
—
—
0.915 0.872 0.830 0.784 0.741
Pipe length
10
20
30
40
32
65
98
131
—
—
0.995 0.993 0.990 0.853 0.828
—
0.998 0.995 0.993 0.990 0.853 0.828
1.000 0.998 0.995 0.993 0.990 0.853 0.828
0.990 0.988 0.985 0.983 0.980 0.843 0.818
—
0.978 0.975 0.973 0.970 0.833 0.808
—
—
0.965 0.963 0.960 0.823 0.798
6. Capacity compensation rate for pipe length and height difference
50
60
70
164
196
229
50
60
70
164
196
229