1. Specifications Cassette Type Inverter heat pump Model name AUU18RGLX AUU24RGLX Power supply 208/230 V ~ 60 Hz Power supply intake Outdoor unit Available voltage range 187—253 V 5.28 7.03 Rated Btu/h 18,000 24,000 Cooling 1.58—6.30 1.58—8.50 Min.—Max. Btu/h 5,400—21,500 5,400—29,000 6.15 7.91...
Page 9
Cassette Type Inverter heat pump Model name AUU18RGLX AUU24RGLX NOTES: • Specifications are based on the following conditions: – Cooling: Indoor temperature of 80 °FDB (26.67 °CDB) / 67 °FWB (19.44 °CWB), and outdoor temperature of 95 °FDB (35 °CDB) / 75 °FWB (23.9 °CWB). –...
Page 10
Cassette Type Inverter heat pump Model name AUU30RGLX AUU36RGLX AUU42RGLX AUU48RGLX Power supply 208/230 V ~ 60 Hz Power supply intake Outdoor unit Available voltage range 187—253 V 8.79 10.55 12.31 14.07 Rated Btu/h 30,000 36,000 42,000 48,000 Cooling 2.81—10.26 2.81—11.43 5.01—13.19 5.01—14.65...
Page 11
Cassette Type Inverter heat pump Model name AUU30RGLX AUU36RGLX AUU42RGLX AUU48RGLX NOTES: • Specifications are based on the following conditions: – Cooling: Indoor temperature of 80 °FDB (26.67 °CDB) / 67 °FWB (19.44 °CWB), and outdoor temperature of 95 °FDB (35 °CDB) / 75 °FWB (23.9 °CWB). –...
2-3. Installation space requirement Provide sufficient installation space for product safety. For 4-direction setting: • Models: AUU18RGLX and AUU24RGLX Unit: in (mm) Strong and durable ceiling 11 (256) or more 60 (1,500) 119 (3,000) or more or more Ceiling height Ceiling mode* “Low”...
Page 15
For 3-direction setting: Unit: in (mm) 4 (100) or more* NOTES: • To set “3-direction”, optional Air outlet shutter plate (UTR-YDZK) must be installed, and the “out- let-direction” need to be switched to “3-way” by remote controller. *: When installing the indoor unit, be careful about the maintenance space. •...
4. Capacity table Capacity tables show each of following values calculated based on the outdoor temperature and the indoor temperature, under given Airflow Rate (AFR): For cooling capacity: Total Capacity (TC), Sensible Heat Capacity (SHC), and Input Power (IP) For heating capacity: Total Capacity (TC) and Input Power (IP) 4-1.
5-4. Duct connection ¢ Outlet air Duct (inside size: 13-3/4 × 3-15/16 in [350 × 100 mm]) Model: AUU18RGLX 0.40 (100) 0.32 (80) 0.24 (60) L= 3ft 3-3/8in (1m) L= 16ft 4-27/32in 0.16 (40) Fan Speed (5 m) Quiet 1-way L= 32ft 9-11/16in Fan Speed Fan Speed...
Page 46
Model: AUU36RGLX 0.40 (100) 0.32 (80) Fan Speed High 1-way 0.24 (60) L= 3ft 3-3/8in (1m) Fan Speed High 2-way L= 16ft 4-27/32in 0.16 (40) (5 m) Fan Speed L= 32ft 9-11/16in Quiet 1-way (10m) 0.08 (20) Fan Speed Quiet 2-way (71) (141)
Page 47
¢ Precautions on air-outlet duct connection • Connect the air-outlet duct to maximum 2 directions among the 4-duct connecting directions. CAUTION Do not connect ducts at 3 or more directions. • When installing air-outlet duct in 2 directions, connect the ducts in a straight line. Air-outlet duct Close Close...
7. Safety devices Model Type of protection Protection form AUU18-48RGLX Current fuse Circuit protection 250 V, 3.15 A (PCB*) 257 ± 18 °F (125 ± 10 °C) Activate Fan motor stop Fan motor Thermal protection protection program 248 ± 18 °F (120 ± 10 °C) Reset Fan motor restart *: Printed Circuit Board...
8-1. External input • “Operation/Stop” mode or "Forced stop" mode can be selected with function setting of indoor unit. • A twisted pair cable (22AWG) should be used. Maximum length of cable is 492 ft (150 m). • The wire connection should be separate from the power cable line. ¢...
8-2. External output Use an external output cable with appropriate external dimension, depending on the number of ca- bles to be installed. ¢ Indoor unit • A twisted pair cable (22AWG) should be used. Maximum length of cable is 82 ft (25 m). •...
8-3. Combination of external input and output By combining the function setting of the indoor unit and rotary switch setting of the External input and output PCB, you can select various combinations of functions. Combination examples of external input and output are as follows: External input External input Function...
Page 57
External output External input Function and output Indoor unit Mode External input and output PCB setting PCB (Rotary Output CN47 Output 1 Output 2 Output 3 Indoor unit fan 60-00 Operation/Stop Operation/Stop Error status operation status Indoor unit fan External heater 60-00 Operation/Stop Error status...
Page 58
¢ Input signal type • Indoor unit Input signal type is only "Edge". Edge • External input and output PCB The input signal type can be selected. Signal type (edge or pulse) can be switched by the DIP switch 2 (SW2) on the External input and output PCB.
8-4. Details of function ¢ Control input function When function setting is "Operation/Stop" mode 1 • In the case of "Edge" input Rotary SW of Function External input and External input Input signal Command setting / output PCB Off → On Operation Input of indoor unit Terminal...
Page 60
When function setting is "Forced stop" mode • In the case of "Edge" input Rotary SW of Function External input and External input Input signal Command setting / output PCB Off → On Forced stop Input of indoor unit Terminal On →...
Page 61
When function setting is "Operation/Stop" mode 2 • In the case of "Edge" input Rotary SW of Function External input and External input Input signal Command setting / output PCB Off → On Operation Input of indoor unit Terminal Stop (R.C.
Page 62
¢ Forced thermostat off function Function Rotary SW of External External input Input signal Command setting / input and output PCB 60-00 / 2 60-02 / 4 60-05 / 7 Off → On Thermostat off 60-06 / 8 External input and output Input 1 60-08 / A 60-09 / B...
Page 63
¢ Error status Function Rotary SW of External External output Output signal Command setting / input and output PCB Low → High Error 60-09 / B Output of indoor unit CN47 High → Low Normal 60-00 / 2 Off → On Error 60-01 / 3 60-02 / 4...
Page 64
¢ Indoor unit fan operation status Function Rotary SW of External External output Output signal Command setting / input and output PCB Low → High Fan run 60-10 / C Output of indoor unit CN47 High → Low Fan stop 60-00 / 2 Off →...
Page 65
Return air • Inappropriate designing and installation of external heater may cause a fire by emitted heat from the external heater. • Fujitsu General Ltd. is not responsible for inappropriate designing or installation of external heating device. - 59 - 8-4.
Page 66
Auxiliary heater control 1 Operation Condition Heater on Heater is on as shown in following diagram of heating temperature. • Heater is off as shown in following diagram of heating temperature. • Other than heating mode Heater off • Error occurred •...
Page 67
Heat pump prohibition control Perform heating by external heater only. Indoor unit is continuous thermostat off. Operation Condition Heater on Heater is on as shown in following diagram of heating temperature. • Heater is off as shown in following diagram of heating temperature. •...
Page 68
Auxiliary heater control by outdoor temperature 1 This control selects heat pump or external heater according to the outdoor temperature. When out- door temperature is high, the heating is performed by using heat pump only. Operation Condition Heater on Heater is on as shown in following diagram of heating temperature.
Page 69
• Operation status 46.4°F (8°C) 42.8°F (6°C) Outdoor temperature (Factory setting) -0.4°F (-18°C) -4°F (-20°C) Heat pump Heat pump Combination zone prohibition only zone Outdoor temperature zone * zone Comp. On/Off 12 V Heater * The outdoor temperature zone transition from one to another will stay in that zone for minimum of 30 min. NOTE: In following operations, compressor will be on in heat pump prohibition zone.
Page 70
Auxiliary heater control by outdoor temperature 2 This control selects heat pump or external heater according to the outdoor temperature. Even when outdoor temperature is high, the heating is performed by using both of heat pump and external heater. Operation Condition Heater on...
Page 71
• Operation status 46.4°F (8°C) 42.8°F (6°C) Outdoor temperature (Factory setting) -0.4°F (-18°C) -4°F (-20°C) Heat pump Combination zone prohibition Outdoor temperature zone * zone Comp. On/Off 12 V Heater * The outdoor temperature zone transition from one to another will stay in that zone for minimum of 30 min. NOTE: In following operations, compressor will be on in heat pump prohibition zone.
Page 72
¢ Heating thermostat on for humidifier Indoor unit Function External output setting Situation Mode Rotary SW Heating Indoor unit fan Heating thermostat on operation thermostat on no. 60 status 60-05 CN47 Example of 60-06 Output3 individual Not used 60-07 Output2 connection 60-08 Output1...
9. Function settings To adjust the functions of this product according to the installation environment, various types of function settings are available. NOTE: Incorrect settings can cause a product malfunction. 9-1. Function settings on indoor unit By using some components on the PCB, you can change the function settings. ¢...
Page 74
¢ DIP switch setting • SW100: Remote controller address setting NOTE: Because this setting is normally done automatically when 2-core wired remote con- troller is installed, setting is unnecessary. Multiple indoor units can be operated by using one wired remote controller. Set the unit number of each indoor unit.
9-2. Contents of function setting Each function setting listed in this section is adjustable in accordance with the installation environ- ment. NOTE: Setting will not be changed if invalid numbers or setting values are selected. ¢ Function setting list Function no. Functions Filter sign Ceiling height...
Page 76
3) Outlet directions Select the appropriate number of outlet directions according to the installation conditions. Function number Setting value Setting description Factory setting 4-way ♦ 3-way 4) Vertical airflow direction range control To prevent draft, change the setting to "Upward" (01). Note that the airflow in certain usage conditions may leave the ceiling dirty.
Page 77
5) Room temperature control for indoor unit sensor Depending on the installed environment, correction of the room temperature sensor may be re- quired. Select the appropriate control setting according to the installed environment. The temperature of the room temperature sensor is corrected as follows: Corrected temp.
Page 78
6) Room temperature control for wired remote controller sensor Depending on the installed environment, correction of the wire remote temperature sensor may be required. Select the appropriate control setting according to the installed environment. To change this setting, set Function 42 to Both “01”. Ensure that the Thermo Sensor icon is displayed on the remote controller screen.
Page 79
9) Remote controller custom code (Only for wireless remote controller) The indoor unit custom code can be changed. Select the appropriate custom code. Function number Setting value Setting description Factory setting ♦ 10) External input control "Operation/Stop" mode or "Forced stop" mode can be selected. Function number Setting value Setting description...
Page 80
13) Switching functions for external output terminal Functions of the external output terminal can be switched. For details, refer to “External input and output”. Function number Setting value Setting description Factory setting Operation status ♦ 01—04 Cooling thermostat On Heating operation Operation/Stop 07—08 Cooling thermostat On...
Page 81
16) Outdoor temperature zone boundary temperature A Setting required if changing of the outdoor temperature setting for heat pump prohibition zone is re- quired when auxiliary heater control by outdoor temperature 1 and 2 are performed on the indoor unit. For details, refer to “External heater output” on page 2. Function number Setting value Setting description...
11. Optional parts 11-1. Controllers Exterior Part name Model name Summary Easy finger touch operation with LCD Office Fri 10:00AM Mode Set Temp. Wired remote panel. Backlit LCD enables easy Cool 80°F Custom Auto Auto Heat 74°F UTY-RNRUZ* Cool 84°F Room Temp.
11-2. Cassette grille Exterior Part name Model name Summary This cassette grille to blow airflow in Cassette grille UTG-GCGF 360º direction by unique seamless airflow louver design. This cassette grille to blow airflow in 360º direction by unique seamless Cassette grille UTG-LCGVCB airflow louver design.
Page 85
Wireless LAN UTY-TFSXZ2 smartphones and tablets. adapter For connection indoor unit with UART interface. This converter can control Fujitsu Thermostat UTY-TTRX General products using a third-party converter thermostat controller. NOTE: Combined use of following optional parts and Wireless LAN adapter (UTY-TFSXZ2) is not allowed.
1. Specifications Type Inverter heat pump Model name AOU18RGLX AOU24RGLX AOU30RGLX AOU36RGLX Power supply 208/230 V ~ 60 Hz Power supply intake Outdoor unit Available voltage range 187—253 V Starting current 11.5 16.1 Cooling 1,177 (2,000) 2,119 (3,600) 2,119 (3,600) 2,237 (3,800) Airflow rate CFM (m...
Page 89
Type Inverter heat pump Inverter heat pump Model name AOU42RGLX AOU48RGLX Power supply 208/230 V ~ 60 Hz Power supply intake Outdoor unit Available voltage range 187—253 V Starting current 16.8 20.9 Cooling 3,973 (6,750) 4,061 (6,900) Airflow rate CFM (m...
3. Installation space 3-1. Models: AOU18RGLX, AOU24RGLX, AOU30RGLX, and AOU36RGLX ¢ Space requirement Provide sufficient installation space for product safety. Single outdoor unit installation • When the upper space is open: Unit: in (mm) When there are obstacles at the rear only. When there are obstacles at the rear and sides.
Page 93
• When there is an obstruction in the upper space: Unit: in (mm) When there are obstacles at the rear When there are obstacles at the rear, sides, and and above. above. Max. 19 Max. 19 (500) (500) 40 (1,000) or more 24 (600) or more...
Page 94
Multiple outdoor unit installation • When the upper space is open: Unit: in (mm) When there are obstacles at the rear only. When there are obstacles at the front only. 60 (1,500) or more 10 (250) 12 (300) or more or more When there are obstacles at the front and rear.
Page 95
Outdoor unit installation in multi-row Unit: in (mm) Single parallel unit arrangement Multiple parallel unit arrangement 6 (150) or more 20 (500) or more 79 (2,000) or more 119 (3,000) or more 24 (600) or more 24 (600) or more 60 (1,500) or more 40 (1,000) or more 10 (250) or more...
3-2. Models: AOU42RGLX and AOU48RGLX ¢ Space requirement Provide sufficient installation space for product safety. Single outdoor unit installation • When the upper space is open: Unit: in (mm) When there are obstacles at the rear only. When there are obstacles at the rear and sides.
Page 97
• When there is an obstruction in the upper space: Unit: in (mm) When there are obstacles at the rear and above. Max. 11 (300) 60 (1,500) or more 20 (500) or more - 91 - 3-2. Models: AOU42RGLX and AOU48RGLX 3. Installation space...
Page 98
Construct a canopy and a pedestal, or place the unit on a high stand that is locally installed. - 92 - 3-2. Models: AOU42RGLX and AOU48RGLX 3. Installation space...
6. Capacity compensation rate for pipe length and height difference Height difference H Indoor unit is higher than outdoor unit Indoor unit is lower than outdoor unit Outdoor unit Indoor unit Outdoor unit Indoor unit Connection pipe Connection pipe 6-1. Models: AOU18RGLX, AOU24RGLX, AOU30RGLX, and AOU36RGLX NOTE: Values mentioned in the table are calculated based on the maximum capacity.
6-2. Models: AOU42RGLX and AOU48RGLX NOTE: Values mentioned in the table are calculated based on the maximum capacity. Pipe length COOLING — — — — 0.879 0.847 0.814 0.782 0.743 — — — 0.927 0.894 0.861 0.828 0.795 0.755 Indoor unit is higher —...
9-2. Sound level check point Rear Microphone Microphone Airflow 40 in (1 m) Side view Rear view Rear Microphone Microphone Airflow 40 in (1 m) Side view Rear view NOTE: Detailed shape of the actual outdoor unit might be slightly different from the one illustrated above.
Size 20—16 spec. * Connection Limited cable * wiring ft (m) 167 (51) length Model name Item Unit AOU42RGLX AOU48RGLX Voltage 208/230~ Power supply Frequency MCA *1 25.2 28.3 Starting current 16.8 20.9 MAX. CKT. BKR * Power cable 14—10...
11. Safety devices Model Type of protection Protection form AOU18RGLX Current fuse (Filter PCB) 250 V, 5 A × 2 Circuit protection Current fuse (Main PCB) 250 V, 3.15 A × 2 °F (150 °C) Activate Fan motor stop Fan motor Thermal protection protection °F (120...
Page 115
Model Type of protection Protection form AOU42RGLX AOU48RGLX 250 V, 30 A Current fuse (Filter PCB) 250 V, 10 A × 2 Circuit protection 250 V, 5 A Current fuse (Main PCB) 250 V, 3.15 A 252±16°F (122±9 °C) Activate...
12. External input and output (for 42/48 model) With using external input and output functions, this product can be operated inter-connectedly with an external device. Connector Input Output Remarks CN10 Low noise mode — CN11 Peak cut mode — See external input/output settings for details.
Page 117
¢ Peak cut mode By performing following on-site work, operation that suppresses the current value can be enabled: The air conditioner is set to the “Peak cut mode” when closing the contact input of a commercial timer or on/off switch to a connector on the control PCB of the outdoor unit. •...
12-2. External output With using external output function, some status signals are transmitted to the control PCB, and the related LED lamp indicates the status of this product. ¢ Error status output Signal on air conditioner error status is generated when a malfunction occurs. •...
Page 119
¢ Compressor status output Signal on compressor operation status is generated when the compressor is running. • Circuit diagram example • 1: Power supply Outdoor unit Voltage (Vcc): DC 24 V or less control PCB Connected unit • 2: Load Connector DC 500 mA or less Power...
13. Function settings (for 42/48 model) Perform appropriate function setting locally according to the installation environment. NOTE: Incorrect settings can cause a product malfunction. CAUTION • Before setting up the switch buttons, discharge the static electricity from your body. • Never touch the terminals or the patterns on the parts that are mounted on the PCB. 13-1.
Page 121
¢ Switch buttons and the functions LED lamps Switch buttons LED lamp Function or operation method Lights on while power on. (1) POWER/MODE Green Local setting in outdoor unit or error code is displayed with blink. (2) ERROR Blinks during error operation. (3) PUMP DOWN (L1) Orange Lights on during pump down operation.
13-2. Local setting procedure NOTE: Before performing the function setting, be sure to stop the operation of the air conditioner. ¢ Low noise mode LED lamps Switch buttons Press the MODE switch button (SW1) for 3 seconds or more to switch to “Local setting mode”. After confirming the LED lamp of POWER/MODE blinks 9 times, press the ENTER switch but- ton (SW3).
Page 123
Press the ENTER switch button (SW3) and fix it. PEAK CUT (L4) (L5) (L6) MODE 1: Low MODE 2: Lower To return to “Operating status display (Normal operation)”, press the EXIT switch button (SW4). In case of missing how many times you pressed the SELECT and ENTER switch buttons: 1.
Page 124
Press the ENTER switch button (SW3). LOW NOISE (L2) (L3) PEAK CUT MODE Sign “ ”: Lights on Press the SELECT switch button (SW2), and adjust the LED lamps as shown below. PEAK CUT (L4) (L5) (L6) Blink 0 % of rated input ratio 50 % of rated input ratio Blink 75 % of rated input ratio...
Page 125
14-1. Models: AOU18RGLX, AOU24RGLX, AOU30RGLX, and AOU36RGLX Part name Exterior Q’ty Part name Exterior Q’ty Installation manual Drain cap Drain pipe 14-2. Models: AOU42RGLX and AOU48RGLX Part name Exterior Q’ty Part name Exterior Q’ty Installation manual Drain cap Drain pipe Conduit plate - 119 - 14-1.
Page 126
15. Optional parts Exterior Part name Model name Summary Use to operate the external input and External UTY-XWZXZ3 output functions of outdoor unit. connect kit For 42/48 model - 120 - 15. Optional parts...