Fujitsu AMUG24LMAS Design & Technical Manual page 53

Air conditioner duct type
Hide thumbs Also See for AMUG24LMAS:
Table of Contents

Advertisement

 Auxiliary heat pump control by outdoor temperature 3
• External heater output
Operation
Heater on
DIP-SW101-3
Indoor unit fan
setting for
external heater
Heater off
DIP-SW101-3
Indoor unit fan
setting for
external heater
– Temperature of heater on (Thon): Set temperature (Ts) - 0.9 °F (- 0.5 °C)
– Temperature of heater off: Set temperature (Ts) + 0.9 °F (+ 0.5 °C)
Tr-Ts ≥ 0.9°F
(0.5°C)
• Auxiliary heat pump On/Off
– Temperature of heater on (Thon): Adjustable by function number 62 (Operating temperature
switching of heat pump).
– All control temperatures will shift by adjusting "Thon".
Tr-Ts ≥ -1.8°F
(-1°C)
*: When room temperature stays in this zone for a specific time, auxiliary heater is turned on. For
details, refer to function number 71.
6-4. Details of function
Heater is on as shown in following diagram of heating
temperature.
On
• Heater is off as shown in following diagram of heating
temperature.
• Other than heating mode
• Error occurred
Enabled
• Forced thermostat off
• Fan stop protection
Off
• Heater is off as shown in following diagram of heating
temperature.
• Other than heating mode
Disabled
• Error occurred
• Forced thermostat off
Tr-Ts
Off
Tr-Ts (=Thon) ≤ -0.9°F (-0.5°C)
On
Tr-Ts
Off
*
Tr-Ts (=Thon) < -5.4°F (-3°C)
On
- 49 -
Condition
Tr: Room temperature
Ts: Set temperature
Thon: Heater on temperature
Tr: Room temperature
Ts: Set temperature
Thon: Heater on temperature
6. External input and output