Fujitsu AMUG24LMAS Design & Technical Manual page 64

Air conditioner duct type
Hide thumbs Also See for AMUG24LMAS:
Table of Contents

Advertisement

18) Fan delay time
Sets the fan delay time when the heater is turned off.
Function number
74
19) External heater use in defrosting
Enables or disables external heater use in defrosting.
NOTE: Inappropriate heater selection may cause cold air in defrosting.
Function number
75
20) Airflow adjustment for operation mode
Strong or weak airflow can be set by ±10%.
Since the airflow volume by motor has the upper limit and lower limit, up-down adjustment
may not be performed depending on the models or settings even if this setting is performed.
Function number
92
21) Airflow adjustment at heater only operation
By selecting the heater output in the table below at heater only operation, this function
adjusts the airflow volume according to the heater output to prevent cold air feeling.
Function number
93
7-2. Function settings by using remote controller
Setting value
00
01
02
03
Setting value
00
01
Setting value
Cooling setting
Standard
00
(no change)
Standard
01
(no change)
Standard
02
(no change)
03
+10% up
04
+10% up
05
+10% up
06
-10% down
07
-10% down
08
-10% down
Setting value
00
01
02
03
04
05
- 60 -
Setting description
1 minute
50 seconds
40 seconds
30 seconds
Setting description
Disable
Enable
Setting description
Heating setting
Standard
(no change)
+10% up
-10% down
Standard
(no change)
+10% up
-10% down
Standard
(no change)
+10% up
-10% down
Setting description
Heater output range
No heater
0 — 3.4 kW (Min. CFM)
3.4 — 6.8 kW (350 CFM)
6.8 — 10.4 kW (710 CFM)
10.4 — 13.7 kW (1,070 CFM)
13.7 — 17.1 kW (1,410 CFM)
Factory setting
Factory setting
Factory setting
Factory setting
7. Function settings