Fujitsu AMUG24LMAS Design & Technical Manual page 44

Air conditioner duct type
Hide thumbs Also See for AMUG24LMAS:
Table of Contents

Advertisement

 Auxiliary heater control by outdoor temperature 2
This control selects heat pump or external heater according to the outdoor temperature. Even when
outdoor temperature is high, the heating is performed by using both of heat pump and external
heater.
Operation
Heater on
DIP-SW101-3
Indoor unit fan
setting for
external heater
Heater off
DIP-SW101-3
Indoor unit fan
setting for
external heater
• Temperature of heater on (Thon): Adjustable by function number 62 (Operating temperature
switching of external heaters).
• All control temperatures will shift by adjusting "Thon".
• Outdoor temperature zone boundary A: Adjustable by function setting number 66.
• External heater output
Tr-Ts ≥ 0.9°F
(0.5°C)
*: When room temperature stays in this zone for a specific time, auxiliary heater is turned on. For
details, refer to function number 71.
• Outdoor temperature zone
A + 3.6°F ( 2°C): -0.4°F (-18°C)
*: Adjustable by function setting 66
6-4. Details of function
Heater is on as shown in following diagram of heating temperature.
On
• Heater is off as shown in following diagram of heating temperature.
• Other than heating mode
• Error occurred
Enabled
• Forced thermostat off
• Fan stop protection
Off
• Heater is off as shown in following diagram of heating temperature.
• Other than heating mode
Disabled
• Error occurred
• Forced thermostat off
Tr-Ts
Off
On
Outdoor temp.
Combination zone  
  ( Heat pump + Heater)
A: -4°F (-20°C)*
Heat pump prohibition zone  
 
Condition
*
Tr-Ts (=Thon) < -0.9°F (-0.5°C)
Tr: Room temperature
Ts: Set temperature
Thon: Heater on temperature
(Heater)
- 40 -
6. External input and output

Advertisement

Table of Contents
loading

Table of Contents