 Auxiliary heater control by outdoor temperature 3
This control selects heat pump or external heater according to the outdoor temperature. Even when
outdoor temperature is high, the heating is performed by using both of heat pump and external
heater.
Operation
Heater on
DIP-SW101-3
Indoor unit fan
setting for
external heater
Heater off
DIP-SW101-3
Indoor unit fan
setting for
external heater
• Temperature of heater on (Thon): Adjustable by function number 62 (Operating temperature
switching of external heaters).
• All control temperatures will shift by adjusting "Thon".
• Outdoor temperature zone boundary B: Adjustable by function setting number 67.
• External heater output
Tr-Ts ≥ 0.9°F
(0.5°C)
*: When room temperature stays in this zone for a specific time, auxiliary heater is turned on. For
details, refer to function number 71.
• Outdoor temperature zone
B + 3.6°F (2°C): 46.4°F (8°C)
*: Adjustable by function setting 67
6-4. Details of function
Heater is on as shown in following diagram of heating temperature.
On
• Heater is off as shown in following diagram of heating
temperature.
• Other than heating mode
• Error occurred
Enabled
• Forced thermostat off
• Fan stop protection
Off
• Heater is off as shown in following diagram of heating
temperature.
• Other than heating mode
Disabled
• Error occurred
• Forced thermostat off
Tr-Ts
Off
On
Outdoor temp.
Heat pump only zone
(Heat pump)
B: 42.8°F (6°C)*
Combination zone
(Heat pump + Heater)
Condition
*
Tr-Ts (=Thon) < -0.9°F (-0.5°C)
Tr: Room temperature
Ts: Set temperature
Thon: Heater on temperature
- 42 -