Master Profibus Address - Siemens SIMATIC IM151-1 Manual

Et 200s distributed i/o high feature interface module
Hide thumbs Also See for SIMATIC IM151-1:
Table of Contents

Advertisement

Bit
6
1: The DP slave type does not match the software
configuration.
7
1: Parameters have been assigned to the DP slave
by a different DP master (not the one that currently
has access to the DP slave).
Structure of station status 2 (byte 1)
Table 4- 4
The bit is updated only if another diagnostics message changes also.
1
Structure of station status 3 (byte 2)
Table 4- 5
0 to 6
4.3.4

Master PROFIBUS address

Definition
The Master PROFIBUS address diagnostics byte contains the PROFIBUS address of the DP
master:
● That assigned parameters to the DP slave
● That has read and write access to the DP slave
The master PROFIBUS address is located in byte 3 of the slave diagnostics.
IM151-1 HIGH FEATURE interface module (6ES7151-1BA02-0AB0)
Manual, 03/2008, A5E01075975-02
Meaning
Structure of station status 2 (byte 1)
Bit
0
1: The DP slave parameters need to be reassigned.
1
1: A diagnostics message is pending. The DP slave will not operate until the problem is
eliminated (static diagnostics message).
2
1: The bit on the DP slave is always "1".
3
1: The watchdog is activated for this DP slave.
4
1: The DP slave has received the "FREEZE" control command
5
1: The DP slave has received the "SYNC" control command
6
0: Bit is always "0".
7
1: The DP slave is disabled, that is, it has been removed from the processing in progress.
Structure of station status 3 (byte 2)
Bit
0: Bits are always set to "0".
There are more diagnostics messages pending than the DP slave is able to store.
7
1: •
The DP master cannot enter all the diagnostics messages sent by the DP slave in
its diagnostics buffer (channel-specific diagnostics).
Interrupt, error, and system messages
Cause/Remedy
Has the correct station type been entered in the
configuration software?
The bit is always 1, for example, if you access the DP
slave with the programming device or another DP master.
The PROFIBUS address of the DP master that assigned
parameters to the DP slave is located in the "Master
PROFIBUS address" diagnostics byte.
Meaning
Meaning
4.3 Diagnostics with STEP 7
.
1
.
1
49