Huawei SUN2000-55KTL Series User Manual page 108

Three-phase grid-tied pv string inverter
Hide thumbs Also See for SUN2000-55KTL Series:
Table of Contents

Advertisement

SUN2000-(55KTL, 60KTL) Series
User Manual
Alarm ID
Alarm
Name
318
Abnormal
Residual
Current
321
Cabinet
Overtemp
erature
322
Abnormal
SPI
Communi
cation
326
Abnormal
Groundin
g
400
System
Fault
Issue 06 (2020-01-03)
Alarm
Possible Cause
Severity
Major
Cause ID = 1
The insulation resistance
against the PGND cable at the
input side decreases when the
inverter is running, which
causes an excessively high
residual current.
Major
Cause ID = 1
The inverter is installed in a
place with poor ventilation.
The ambient temperature
exceeds the upper
threshold.
The internal fan works
abnormally.
Major
Cause ID = 1
An unrecoverable fault occurs
on a circuit inside the inverter.
Major
Cause ID = 1
The PGND cable does not
connect to the inverter.
The SUN2000 output side
does not connect to an
isolation transformer when
the PV string output is
grounded.
Major
Cause ID = 1/3/21/23/27
An unrecoverable fault occurs
on a circuit inside the inverter.
Copyright © Huawei Technologies Co., Ltd.
8 System Maintenance
Suggestion
1. If the alarm occurs accidentally,
the external circuit may be
abnormal temporarily. The
inverter automatically recovers
after fault is rectified.
2. If the alarm occurs repeatedly or
persists, check whether the
impedance between the PV string
and the ground is excessively
low.
1. Check the ventilation and
ambient temperature of the
inverter installation position.
2. If the ventilation is poor or the
ambient temperature exceeds the
upper threshold, improve the
ventilation and heat dissipation.
3. If the ventilation and ambient
temperature both meet
requirements, contact Huawei
technical support.
Turn off the AC output switch and
DC input switch. Then turn on the
AC output switch and DC input
switch after 5 minutes. If the fault
persists, contact Huawei technical
support.
1. Check that the PGND cable
properly connects to the inverter.
2. If the PV string output is
grounded, check that the
SUN2000 output side connects to
an isolation transformer.
Turn off the AC output switch and
DC input switch. Then turn on the
AC output switch and DC input
switch after 5 minutes. If the fault
persists, contact Huawei technical
support.
102