4

Technical data

General data and operating conditions

Conformity and approval
Conformity
CE
EAC
Approval
UR
Protection of persons and equipment
Enclosure
Thermal contact
Design
Switching
capacity
Environmental conditions
Climate
Storage
Transport
Operation
Site altitude
Vibration
resistance
2
(9.81 m/s
= 1 g)
Mounting conditions
Mounting
location
Mounting
position
Free space
at the top
at the bottom
to the sides
EDKRBM390R DE/EN/FR/ES/IT 3.1
General data and operating conditions
2006/95/EC
TP TC 004/
2011
(TR CU 004/
2011)
UL508
IEC/EN
60721−3−1
IEC/EN
60721−3−2
IEC/EN
60721−3−3
EN 50178,
IEC 61800−5−
1,
Germanisch
er Loyd,
general
conditions
l
Technical data
Low−Voltage Directive
On safety of low
voltage
equipment
Industrial Control Equipment,
Underwriter Laboratories (File−No.
E208678) for USA and Canada
IP50
NC contact, 200 °C
250 V AC / 2 A
1K3 (−25 ... +60 °C)
2K3 (−25 ... +70 °C)
3K3 (−10 ... +55 °C)
Current derating from +45 ... +55 °C:
2.5 %/°C
0 ... 4000 m amsl
1000 ... 4000 m amsl: Current
derating 5 %/1000 m
Acceleration resistant up to 1 g
l
In the control cabinet
l
The mounting location must
comply with the device features
mentioned in the chapter "General
data".
l
Flammable materials or
substances may not be placed in
the vicinity of the brake resistor.
l
The heat generated by the brake
resistor must be dissipated freely.
Vertically suspended with connecting
cables at the bottom.
> 200 mm
> 100 mm
> 30 mm
Eurasian
Conformity
TR CU: Technical
Regulation of
Customs Union
4
35