Download Print this page

Advertisement

Quick Links

CDP-TW-K-BSY+ instructions
Please order bracket sets separately

Advertisement

loading

Summary of Contents for D+H Dyer CDP-TW-K-BSY+ Series

  • Page 1 CDP-TW-K-BSY+ instructions Please order bracket sets separately...
  • Page 2 Failure to follow all instructions listed below may - Operating voltage 230 V AC result in electric shock, fire and/or serious injury. - Useable for smoke ventilation, D+H Euro-SHEV according to DIN EN 12101-2 as well as Save all warnings and instructions for future daily natural ventilation reference.
  • Page 3: Technical Data

    Technical data Type CDP-TW 1600-K-BSY+ CDP-TW 2000-K-BSY+ CDP-TW 3000-K-BSY+ Power supply 230 V AC, +10 % / -15 %, 50 Hz Power consumption 100 W / 142 VA 120 W / 160 VA 160 W / 214 VA Nominal force 2 x 800 N 2 x 1000 N 2 x 1500 N...
  • Page 4 Emergency control / Zeroing Emergency control (only synchronous group) BSY+ synchronous control regulates and monitors the difference in position between the drives (max. 30 mm). In the event of an error, all drives are stopped. Before the decision is made to run the drives in auxiliary mode, the cabling should be checked.
  • Page 5: Maintenance And Cleaning

    D+H maintenance notes. Only original from date of verified handing over of the system up D+H spare parts may be used. Repair is to be carried to maximal 3 years after date of delivery, when out exclusively by D+H.
  • Page 6 Connection Cable mounting ~ 35 mm ~ 80 mm Cable dismounting = inverse order CDP-TW-K-BSY+...
  • Page 7 Connection Pin Assignment Standard GN (Data B) YE (Data A) BU (N) BN (Ls) BK (Lr) YE/GN ( (GN) green (YE) yellow (BU) blue (BN) brown (BK) black (WH) white (PK) pink (GY) grey Option -SGI GN (Data B) YE (Data A) BU (N) BN (Ls) BK (Lr)
  • Page 8 Connection Pin Assignment Option -SA-SZ GN (Data B) YE (Data A) BU (N) BN (Ls) BK (Lr) YE/GN ( GN (SZ) GY (SZ) max. YE (SA) 50 V / 0,5 A PK (SA) OG (n.c.) WH (n.c.) BN (n.c.) Option -SGI-SA-SZ GN (Data B) PK (SGI +)
  • Page 9: Risk Of Electric Shock

    Connection Junction box CDP-TW-K-BSY+ * Data b (GN) Protect against short circuit Data a (YE) (YE/GN) (BU) (BN) (BK) to Central ast-mode SHEV High-Speed Normal operation High-Speed 230 V AC / 50 Hz Do not reverse L+N! Connect PE! * Programmable via SCS software and BI-BT 2. Plug in the BI-BT 2 only under tempered conditions. RISK OF ELECTRIC SHOCK! B I - d it...
  • Page 10 Dimensions 67 mm Stroke Weight Standard 800 mm 16,6 kg 1672 mm 401 mm 870 mm 1000 mm 17,7 kg 1200 mm 19,7 kg 2002 mm 401 mm 1200 mm 1500 mm 21,4 kg Minimum construction 600 mm 14,9 kg 1418 mm 401 mm 616 mm...
  • Page 11 Dyer Environmental Controls Ltd Unit 10 Lawnhurst Trading Estate, Cheadle Heath, Stockport SK3 0SD Tel: +44 (0)161 491 4840 E-Mail: enquiry@dyerenvironmental.co.uk www.dyerenvironmental.co.uk...