Technical data

Type
Power supply
Power consumption
Nominal force
Nominal locking force
Lifetime ***
Reliability
Duty cycle
Housing
Ingress protection
Temperature range
Fire stability
Nominal stroke length *;** See type plate
Additional functions *
*
Programmable with software SCS
** 1000 mm max. according to VdS 2580
*** (500 mm) according to VdS 2580
Running speed and forces
Forces
CDP-TW 1600
OPEN
2 x 800 N
CR III
2 x 800 N
CR II
2 x 800 N
CR I
2 x 500 N
Closing edge protection
In the "CLOSE" direction the drive has an active protection
for the main closing edge. If there is an overload in the closing
range 3 and 2, the drive runs "OPEN" for 10 seconds, then
"CLOSE" again. If after three attempts closing is not possible,
the drive remains in this position.
In addition, the drive is equipped with passive protection. The
closing speed in closing range 2 and 1 is reduced to 5 mm/s.
There are still substantial forces that
pose a risk to life and limb.
Significantly greater forces can be
exerted at the secondary closing
edges. Danger of crushing hands and
fingers!
CDP-TW 1600-K-BSY+ CDP-TW 2000-K-BSY+ CDP-TW 3000-K-BSY+
230 V AC, +10 % / -15 %, 50 Hz
100 W / 142 VA
2 x 800 N
2 x 1500 N
>10 000 double strokes
Re = 400
30 % S2 (EN 60034-1), no continuous voltage
Aluminium, PC/ABS (end covers)
IP 32
-5 ... +75 °C
30 min / 300 °C
Closing edge protection activated (3 stroke repeatings),
locking relief activated (0,3 mm)
CDP-TW 2000
CDP-TW 3000
2 x 1000 N
2 x 1500 N
2 x 1000 N
2 x 1000 N
2 x 1000 N
2 x 1000 N
2 x 500 N
2 x 500 N
120 W / 160 VA
2 x 1000 N
Normal operation =
SHEV- fast running =
All forces
+ approx. 20 % switch-off reserve (temporary)
160 W / 214 VA
2 x 1500 N
Main closing edge
CDP-TW-K-BSY+