Menu

A) MAIN MENU (FIGURE 2.2)
The LCD panel indicates power flow and measured values, while also operating the
start/stop function. The LCD panel also allows the user to verify the status and operation of
the UPS Module.
The following will be displayed when the START/STOP key on the LCD panel is pressed:
1) Start/Stop screen (FIGURE 2.3)
The display indicates the start and stop operations for the UPS system. If this operation
is PIN protected, the user is required to enter the security PIN before the screen can be
accessed. Refer to (FIGURE 2.4).
When in remote mode, the message "REMOTE operating model" will appear on this
Screen. The user cannot operate the start and stop functions without changing the
setup from remote mode to local mode.
When bypass voltage is abnormal, the message "Bypass voltage abnormal" will appear.
-Start: When the bypass voltage is abnormal, the LCD asks the operator if an
interrupted transfer is acceptable (Load may be lost). (FIGURE 2.5)
-Stop: When the bypass voltage is abnormal, the user cannot transfer from inverter to
bypass line.
G8000MM
Installation and Operation Manual

FIGURE 2.2 Main screen