B) Shut-down Procedure
If a total UPS shutdown is required, verify that the critical load is OFF.
Shut-down of UPS
1. Press the "START/STOP MENU" from the Main Menu on the LCD.
!
When "REMOTE OPERATION MODE" is displayed on the LCD panel, the inverter stop
operation can only be performed remotely. If local inverter stop operation is required (at the
UPS), select "LOCAL" in "Remote/Local" selection in setup page. Select "LOCAL" mode
for the purpose of this stop procedure.
NOTE
2. Press both "STOP" keys in order on the LCD.
(First press "STOP" key on the left, then press "STOP" key on the right.)
3. In general, only the Inverter will be stopped and the Rectifier will remain energized to
charge the batteries.
Opening the user supplied External Input AC Circuit Breaker (if dual source used),
the External Bypass Input Circuit Breaker and the DC Disconnect Circuit Breaker,
CB2, will shut down the load.
4. If stopping both the Rectifier and Charger is required, open the Battery Disconnect circuit
breaker (CB2) manually.
5. If a dual source is feeding the UPS, open the External AC Rectifier Input Circuit Breaker
(user supplied) manually.
6. If turning off all power to the critical load is desired, open the External Bypass Input
Circuit Breaker (user supplied) manually.
7.
FIGURE 3.5.b Shut-down Procedure
540V
G8000MM
Installation and Operation Manual
To Stop - In order,
first press left stop
key then press right
stop key.
ress both keys
in order
57